PVC(XLPE)InsulatedFire-Resistant Power Cable
1.The product is manufactured according to the standard of GB12706 and GB12666 or IEC,BS,DIN,ICEA,and JIS upon request.
2.The product is suitable for use in power distribution lines or fixed installations with rated power-frequency voltage up to and including 0.6/1kV.
3.Rated power-frequency voltage U0/U:0.6/1kV.
4.Max.permissible continuous operating temperature of conductor (PVC/XLPE): 70℃/90℃
5.XLPE:250℃
Max.short-circuit temperature of the conductor shall not exceed(5s maxiumduration):
PVC:cross-section of conductor≤300mm2-160℃
cross-section of conductor>300mm2-140℃
6.The ambient temperature under installation should not below 0℃
7.The bending radius of a single-core cable should not less than 20 times of the cable diameter.
The bending radius of multicore-cable should not less than 15 times of the cable diameter.