Diesel generating set
Negotiable /Set
Min.Order:1 Set
Singfo Electrical Device Engineering Co.,Ltd.
Model: SFCD450K
50Hz
Continuous power 400kw(500kva) Output voltage 380/440V
Standby power 450kw(563kva) Rate Speed 1500r/min
Price :
USD EXW SINGFO
USD FOB SHENZHEN
Technical parameters of Gen-Set:
Power factor COSΦ=0.8lagging
Start mode Electric
Noise level 80-100dB
Packing dimension 3410*1260*1980MML*W*H
Fuel consumption: 92.1L/H(101.6L/H)
Weight 4150Kg
Rated currency(amps) 855amps
Protection Low oil-pressure, High water temperature,
Over-speed, Over-current.
Technical parameters of Engine:
Brand Cummins Power(50Hz) 450kw
Model KTA19-G4 Original China
Cylinders 6 Cylinders Layout Line
Fuel 0# light diesel Voltage Control AVR
Start mode DC24V electric start Overload 110%
Inter-Cooling Air inter-cooling Displacement 18.9L
Speed-Governing Electric Steady Speed Droop ≤1%
Technical parameters of Alternator:
Brand Stamford Protection IP21
Model HCI544D Original China
Frequency fluctuation ≤±0.5 % Frequency regulation ≤±0.5 %stable
Voltage distortion 4% Voltage control AVR
Technical parameters of Control Panel:
Brand UPWIN 2210
Start or Stop Generator set manually/ Automatically Generator over/under frequency protection
Open controller output can be defined as Pre-heat/Idle output Generator over/under/unbalance voltage Protection
High Coolant temperature protection Over speed protection
Low Oil pressure protection Over speed protection
Over load protection Available for remote control
Noteindicate this function depend on the set points of the controller in field
*Standard Accessories*
1. Accessories.
The standard accessories
Single-bearing generator again drops. IP21. Insulation H
Radiator for 50 ambient temperature and double-deck cooling
The Electric start and 24v charger
Regulator
Standard air filter
Automatic control panel
Storage battery
Switch for out-wire
Steel base-frame against vibration
Soft pipe for fuel and handle for lube going-out
Operation manual
Plastic packing
2. Testing conditions.
Standard Air Intake Temperature 25ºC
Air Intake Pressure 100kpa
Standard Light Diesel 0# or 10# Light diesel
Fuel Intake Temperature 40ºC
Air Intake Restriction 254mmHg
Exhaust Back Pressure 76mmHg
Lubricant Oil 15W40-CF4 Upgrade
3. Operation.
Continuous power: operate continuously for 24h in a day. 10% overload for
An hour is allowed in a 12 hours.
Standby power: this is used only when the civil power is off. Overload is not allowed.
*Optional Accessories*
It is necessary to pay additional if you need these accessories as follows:
ATS (Automatic transfer switch)
ATS is such a system that can exert the function automatically by transferring two circuits to recover power supply while powering off, in stead of manual work.
MCCB (Breaker)
Battery charger
Power factor COSΦ=0.8lagging
Start mode Electric
Noise level 80-100dB
Packing dimension 3410*1260*1980MML*W*H
Fuel consumption: 92.1L/H(101.6L/H)
Weight 4150Kg
Rated currency(amps) 855amps
Protection Low oil-pressure, High water temperature,
Over-speed, Over-current.