Name: Power Cable
Main Applications of Power Cable:
Rated voltage U0 / U were 0.6 / 1 KV, 1.8/3KV, 3.6/6KV, 6/6KV, 6/10KV, 8.7/10KV,
8.7/15KV, 12/20KV, 21/35KV, 26/35KV;
Conductor long-term work to allow the maximum temperature of 90 , short-circuit (the longest duration of not more than five seconds), the Power Cable conductor of the maximum
temperature does not exceed 250 ;
DC Resistance
Conductor with the provisions of GB/T3956;
Laying the ambient temperature of not less than 0 , less than 0 to be heated.
Minimum bend radius of not less than 15 times the Power Cable diameter;
Not drop restrictions on the laying of cables;
Frequency tolerance voltage test:
U0 to 1.8 KV and below cable: 2.5 U0 +2 KV/5min not breakdown,
U0 to 3.6 KV and above cables: 3.5 U0/5min not breakdown,
Partial discharge test:
U0 for more than 3.6 KV and Power Cable, 1.73 U0 under partial discharge of not more than 10 PC
Fire-retardant features:
Flame-retardant cables can withstand GB12666.5 (IEC332-3) under the beam into a combustion test.
Low Smoke low halogen flame retardant Power Cable can withstand GB12666.5 (IEC332-3) under the beam into a combustion test, and when the smoke of burning should be consistent with GB12666.7 (IEC1034) the provisions of combustion gases in the HCL precipitation levels should be ≤ 100 mg / g, and in accordance with the requirements of IEC574-1.
Low Smoke low halogen fire-retardant Power Cables can withstand GB12666.5 (IEC332-3) standard which is under the beam into a combustion test, and when the burning smoke should be consistent with GB12666.7 (IEC1034) the provisions of burning gas solution precipitated the PH value of ≥ 4.3, Conductivity ≤ 10 us / mm, and in accordance with the requirements of IEC754-2.
Fire-resistant Power Cables can reach GB12666.6 (IEC331) standard which provides the fire resistance test.