PVC INSULATED SINGLE PHASE CONCENTRIC COPPER CABLES

PVC INSULATED SINGLE PHASE CONCENTRIC COPPER CABLES

Negotiable /Piece

Min.Order:3 Pieces

Supply Ability:
0 Piece / Pieces per Month
Payment Terms:
T/T L/C D/P D/A
Delivery Detail:
7 days

Quick Details View All >

Brand Name:
Sanhe
Place of Origin:
China
Model Number:
concentric copper cable

Zhengzhou Sanhe Cable Co., Ltd.

Business Type: Trading Company
Main Products: Power Cable , Overhead Cable , Bare conductor

Product Details

1.Scopes

This specification is for PVC insulated single phase concentric cables with circular stranded copper conductors for operation up to and including 1000 Volts between phases and 600 Volts to earth .The cable shall have a central phase stranded copper conductor insulated with red PVC and concentric layer comprising bare copper wires (combined neutral-earth conductor)and outer sheath in black PVC.

2.REQUIREMENT

2.1 SERVICE AND SYSTERM CONDITIONS

a)The cable shall be a service cable for continuous operation outdoors and tropical conditions (temperature range of -1°Cto +40°C,humidity of upto 90% and saline conditions along the coast).

b)The cable should be suitable for laying in cable ducts ,in air of underground.

c)Permissible continuous loading operating temperature shall be 70°C.

2.2 MATERIALS AND CONSTRUCTION

2.22Phase conductor

2.221The phase conductor shall be circular stranded annealed copper conductors (class 2)The phase conductor shall have a left -hand director of lay.

2.222 The insulation of the phase conductor shall be red PVC.It shall be applied by an extrusion process and shall be spark tested..

2.23 Concentric layer

2.231The neutral conductor shall be concentric and shall be manufactured from plain annealed copper wires .

2.24  Oversheath

2.241 The ocersheath shall be an extruded layer of black PVC

2.3 STANDARD SIZES AND CHARACTERISTICS

2.31 The characteristics of the cables shall comply with the following cable.

Table 1:Characteristics (as per KS 04-1022)

 

     Phase Conductor

 

 

 

Concentric

neutral

conductor

number/

approx

dia.of

wires

No./mm

 

 

 

Minim-

um lay

lengths

mm

 

 

Thickness

Of

Oversheath  mm

 

Approxi-mate

overall

Diameter mm

 

 

 

Maximum

Conductor

DC resistance per 1000m

at 20°C

 

 

Phase

ohms

 

Neutral

ohms

 

Nominalarea

mm 2

No./

Approx

dia. of wires mm

Thickness

of

Insulation mm

 

10

7/1.35

1.55

20/0.85

140

1.4

11.73

1.83

1.151

 

16

7/1.70

1.55

32/0.85

152

1.4

12.78

1.15

1.007

 

25

7/2.14

1.60

29/1.13

165

1.5

14.88

0.727

0.629

 

Contact Supplier

Ms Anna Zhang Manager Chat Now
Telephone
86-371-69176007
Mobile
86-37169176007
Fax
86-371-69176006
Address
Zhengzhou New District Heze,Shandong

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Electrical Equipment & Supplies > Wires, Cables & Cable Assemblies > Electric Cable
Categories
Hi~