Explosion Proof Area Hydrogen Monitor provides hydrogen-specific leak detection and measurement for hydrogen concentrations as low as 4000 ppm and can be scaled to any concentration up to 5% hydrogen by volume, a range representing 10% to 125% of hydrogen’s lower flammability limit. The monitor is designed for either ceiling or wall mount and has an RS422 capability that extends the interface from the Sensor Module to the Control Module to several hundred feet. H2scan's hydrogen-specific sensor technology has no cross sensitivity to other combustible gases, thus eliminating false positive alarms and ensuring safety system reliability.
Performance
Hydrogen Sensitivity Range:
0.4% to 5.0% hydrogen by volume
10% to 125% hydrogen lower flammable limit
Accuracy: ± (0.03 x indication + 0.2) percent hydrogen by volume
Typical Response Time: T90 of 60 sec maximum
Ingress Protection: IP66
Calibration Interval: 90 days
Product Life Expectancy: 10 years
Interface Options
Input Voltage Range: 90 VAC to 260 VAC
Input Power: 15 W
Analog Output: 4 mA to 20 mA
Serial Communication: RS422
Relay Contacts: Two programmable 5 A, 250 VDC / VAC
SPDT relays with both normally open (N.O.) and
normally closed (N.C.) contacts
Operating Conditions
Operating Temperature Range: 4ºC to 40ºC
Storage Temperature Range: -40ºC to 50ºC
Calibration Background Gas: Air
HY-ALERTA™ 2600 Includes
Sensor Module
Control Module
Infrared Remote Control
Dimensions
Sensor Module
Width: 13.8 cm (5.4 in.)
Length: 19.3 cm (7.6 in.)
Depth: 13.0 cm (5.1 in.)
Control Module
Width: 13.8 cm (5.4 in.)
Length: 14.3 cm (5.6 in.)
Depth: 14.4 cm (5.7 in.)