1MV / 3-Phase AC Relay Test Set K1063+ with VGA Video Interface

1.Easy test
2.Operation menu, Simple operation
3.Power:1000VA

Main specifications:

Voltage generators

Setting 

Range

4-phase AC (L-N)

4 x 0 ... 130 V 

2-phase AC (L-L)

2 x 0 ... 260 V

Power

4-phase AC (L-N)

4 x 70VA,  at 0 ... 130 V

2-phase AC (L-L)

2 x 140VA,  at 0 ... 260 V

Accuracy

<0.07% reading + 0.03% range guaranteed at 0-130V 

<0.04% reading + 0.01% range typical at 0-130V

Resolution

1mV

Current generators

Setting 

Range

6-phase AC (L-N)

6 x 0 ... 30 A

3-phase AC (2L-N)

3 x 0 ... 60 A (Group A II B)

1-phase AC (6L-N)

1 x 0 ... 180 A 

Power

6-phase AC (L-N)

6 x 150 VA , at 0 ... 30A Max 250VA, with the other current channels unload

3-phase AC (2L-N)

3 x 300VA,  at 0 ... 60A (Group A II B) Max 450VA,  with the other current channels unload

1-phase AC (6L-N)

1 x 900 VA

Accuracy

<0.14% reading + 0.06% range guaranteed at 0-40A 

<0.05% reading + 0.02% range typical at 0-40A

Resolution

1mA

Generators,  general

Frequency

Range

0 ... 1000 Hz

Accuracy / drift

Error < 0.001Hz at 10 ... 65Hz,

Error < 0.01Hz  at 65Hz...450Hz

Error < 0.02Hz  at 450Hz...1000Hz

Resolution

0.001Hz

Phase

Range

- 360° ... +360°

Accuracy / drift

Error < 0.2 °

Resolution

0.1°

Time

Range

0 ... 999, 999.999s

Accuracy / drift

Error<0.1ms

Resolution

1ms

DC generators

Voltage ranges

0 ... 300V/180VA 

Current ranges

0 ... 20A/300W

Accuracy

Error<0.1% reading + 0.1% range guaranteed at 0…300 V;

Error <0.1% reading + 0.1% range guaranteed at 

0...20 A;

Resolution

1mA; 1 mV

Harmonic

Harmonic superpose times

2 ... 20

Contact Supplier

Miss. Vicky sale Manager Chat Now
Telephone
86-755-83418941
Mobile
86-83418941
Fax
86-755-88352611
Skype
kingsine_internation
Address
6/F, Block 4-CD, TianAn Cyber Park Shaoxing,Zhejiang

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Health & Medical > Health Care Products > Health Care Supplies > Other Healthcare Supply
Categories
Hi~