Barriers
Negotiable /Set
Min.Order:1 Set
1、Technical Parameters:
1)main functions and features
① compact and clip-mounting
② one input & one output circuit is intrinsically safe,[Exib]IIC
① Transfer the DC signal to isolated standard process signal, and prevent hazardous energy from the instrinsically safe terminal entering into the hazardous.
② With power indicator, Zero & Span adjustment for output signal
③ Two independent input channels & output channels, each channel “input, output and power supply” are isolated from each other
2) hazardous-area signal
1st channel:
① current input: current: 4~20mA,
voltage supply:18.5V~28.5V
Input resistance: 50Ω(built-in)
② voltage input: voltage: 1~5V,
input resistance: ≥50KΩ
③ RTD input(Pt100): input signal: -200℃~+800℃
2nd channel:
① current output : current: 4~20Ma,
load resistance: ≤500Ω
② voltage output : voltage: 1~5V,
load resistance: ≥10KΩ
3)safe-area signal
1st channel:
① current output: current: 4~20mA,
Load resistance: ≤500Ω
② voltage output: voltage: 1~5V,
load resistance: ≥10KΩ
2nd channel:
① current input: current :4~20mA,
input resistance:50Ω
② voltage input: voltage: 1~5V,
input resistance: ≥50KΩ
4) Intrinsic safety:
① Explosion-proof: [Exib]IIC
② max. voltage Um:250V
③ max. output voltage Uo:30V
④ max. external inductance Lo:10Mh
⑤ max. external Capacity Co:0.066 μF
5) environment parameters:
① power supply:DC24V±10%,
power consumption:5W, when ripple coefficient Wpp<10%.
② Temperature: -20~+60℃
③ Humidity:10%~85%RH(no condensation)
2、performance index(to full span)
① standard precision: ±0.2% FS
② temperature drift: ±0.2%/℃
③ Response time: ≤0.5s(0→90%)
④ Affect of power voltage change: ±0.2%/permitted range
⑤ Insulated resistance:
Input, output and power supply are isolated from each other≥50MΩ/DC 500V
⑥ Isolation intensity: input –output-power supply-ground:
DC 1500V/1 minute (DC power)
AC 1500V/1 minute (AC power)
⑦ Affect of load resistance change: ±0.2%/500Ω(current output)
±0.2%(when voltage output)
⑧ Settling time: ≤3s
3、construction and dimension
① structure: compact, clip-mounting
② connection:3mm connection terminal
③ terminal screw material: nickel-plated iron
(screw allowed torque:<0.8N°m)
④ shell material: burn-bear colophony
⑤ isolation: channel isolation (input, output and power supply are isolated from each other)
⑥ zero adjustment range:-5~+5%
⑦ span adjustment range:95~105%
⑧ power indicator: Green LED, light when power on.
⑨ Mounting: DIN rail
⑩ Outline dimension(WxHxD):45.5x100x0113.5mm