4 Phase AC Relay Test Set , 50 Overcurrent Test K5063s

4 Phase AC Relay Test Set , 50 Overcurrent Test K5063s

Negotiable /Piece

Min.Order:1 Piece

Supply Ability:
0 Piece / Pieces per Month
Payment Terms:
T/T L/C D/P D/A
Delivery Detail:
7 days

Quick Details View All >

Brand Name:
Kingsine
Place of Origin:
China
Model Number:
K5063s

Kingsine Electric Automation Co., Ltd,

Business Type: Trading Company
Main Products: Protection Relay Testing ,Relay Test Set ,Relay Test System

Product Details

Delivery Time:15 working days
Certification:ISO9001,CE

4-Phase AC Relay Test Set , 50 Overcurrent Test K5063s

10.4 large LCD screen
4 pairs Binary output
Capacity:250V/3A AC/DC
74-phase AC

Latest Technology make you stand ahead!

K50 series relay tester with latest technology, extremely design for your now and funture use, with power PC software, unique features and functions helps you stand ahead of your competitors!

1. Adopts 10.4 large LCD screen, and provided with VGA video interface, making it available to connect to projector for training;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A(Poleless and adjustable);
5. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
6. Function of transducer and energy meter testing (optional function);
7. Adopt Smart and stable Window CE embedded system. Windows has the advantage of small application program with fast speed, which overcomes the problem of bad stability, easy-damage hardware, and virus of Windows 98/2000/XP;
8. Use high-speed CF card as the storage, more stable, anti-shock compared with ordinary hardware, so works more reliable.

Technical Data of K5063s

Voltage generators

Setting 

Range

4-phase AC (L-N)

4 x 0 ... 300 V 

2-phase AC (L-L)

2 x 0 ... 600 V

Power

4-phase AC (L-N)

4 x 110VA,  at 0 ... 300 V

2-phase AC (L-L)

1 x 110VA,  at 0 ... 600 V

Accuracy

<0.07% reading + 0.03% range guaranteed at 0-300V

<0.04% reading + 0.01% range typical at 0-300V

Resolution

1mV

Current generators

Setting 

Range

6-phase AC (L-N)

6 x 0 ... 15 A

3-phase AC (2L-N)

3 x 0 ... 30 A 

1-phase AC (3L-N)

1 x 0 ... 90 A 

Power

6-phase AC (L-N)

1x 300VA , at ....15A 

3-phase AC (2L-N)

3x 450VA,  at ….30A 

1-phase AC (3L-N)

1 x 1500 VA,  at ...90A(Max)

Accuracy

<0.07% reading + 0.03% range guaranteed at 0-15A 

<0.02% reading + 0.01% range typical at 0-15A

Resolution

1mA

Generators,  general

Frequency

Range

0 ... 1000 Hz

Accuracy / drift

Error < 0.001Hz at 10 ... 65Hz,

Error < 0.01Hz  at 65Hz...450Hz

Error < 0.02Hz  at 450Hz...1000Hz

Resolution

0.001Hz

Phase

Range

- 360° ... +360°

Accuracy / drift

< 0.2 °

Resolution

0.1°

Timer

Range

Infinite

Accuracy / drift

1ms

DC generators

Voltage ranges

0 ... 300V

Contact Supplier

Miss. Vicky sale Manager Chat Now
Telephone
86-755-83418941
Mobile
86-83418941
Fax
86-755-88352611
Skype
vicky.qiu8
Address