Hermitically Sealed Single Phase Kwh Meter MCB Surge Electric Meter Safety

Hermitically Sealed Single Phase Kwh Meter MCB Surge Electric Meter Safety

Negotiable /Set

Min.Order:1 Set

Supply Ability:
0 Set / Sets per Month
Payment Terms:
T/T L/C D/P D/A
Delivery Detail:
7 days

Quick Details View All >

Brand Name:
Calin
Place of Origin:
China
Model Number:
DDSY168-E

Shenzhen Calinmeter Co,.LTD

Business Type: Trading Company
Shenzhen Guangdong China
Main Products:

Product Details

Delivery Time:30 days
Certification:CE/SABS/IEC

Hermitically Sealed Single Phase Kwh Meter MCB Surge Electric Meter Safety 

The DDSY168-E is an economy type sinle phase prepayment meter. It is built in keypad based compact BS footprint housing equiped with a extended transparent terminal cover fitting with MCB. The meter is a cost-effective controller for revenue collection and credit dispensing in low voltage residential environments. Thanks to its dynamic range of 5(80)Amp current and 30Vm Rf withstand immunity, the meter is operatable even in very harsh environments.

The DDSY168-E  upper closure is made of poly-carbonate flame retardant material ,hermitically sealed against illegal intrusion. It isintended for rich metering features to provide a broad range of information such as V, A, PF, P, balance. It also supports tamper detection and SRE (significant reverse energy) measurement for active energy.

The meter provides a metal backplate fixture . This feature enables the meter to be tightly fixed agaisnt the mounting surface to prevent tamper and sabtage.

Major Features

a) Display trip status

b) Programmable power limit and low credit warning

c) Unidirectional measurement for active energy

d) Display valuable meter information by inputting short codes

e) Optical port data output

f) IP 54 rating

g) Surge protection for up to 13kV lightening

 Key benefits

1) Low cost and easy to deploy and maintenance

2) Compact, and durable

3) Tamper proof for revenue protection

4) LED consumption indicator

5) Muti-rate and holiday setting

Specifications:

Nominal voltage Un

220/230/240 V

Limited voltage

70%~120%Un

Nominal frequency fn

50-60Hz+5%

Basic current(Ib)

5-10A

Maximum current(Imax)

60-100A

Starting current(Ist)

20mA

Active energy constant

1000imp/kWh

Accuracy as Active energy to IEC62053‐21

Class1.0

Power consumption in Voltage circuit

<2W  <8VA

Power consumption in current circuit

<1VA

Operating temperature

25℃ to+70℃

Storage temperature

40℃ to+85℃

Insulation level

4kV rms for 1min

Impulse voltage withstand

8kV, 1.2/50 μs

Air discharge

16kV

Immunity to HF fields

80MHz to 2GHz with load

10V/m

100kHz to 1GHz without load

30V/m

Fast transient burst test

4kV

Meter shell Protection Rate

IP54(IEC60529)

Insulation System Classification

 Protective Class II

Contact Supplier

Mr. Edward sale Manager Chat Now
Telephone
86-755-23012661
Mobile
86-18938169306
Fax
86-755-23012661
Skype
rzmx_mo
Address
Block 3 Chaohuilou Inustrial Park, Longhua, Shenzhen, China Weinan,Shaanxi

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Electrical Equipment & Supplies > Electronic & Instrument Enclosures