Product Details

Multi-Secondary Isolation Voltage Transformer Testing Single Phase Meter With Closed I-P link

Brand Name GENY
Place of Origin China
Model Number HJ-200GL

Product Features

Delivery Time:30 days after order confirmed
Certification:ISO 9001
Description:

Multi-Secondary Voltage Transformers test single phase meter with closed I-P link by producing 1:1 ratio isolation voltage 

Technical Specifications:

Primary voltage:

200-400 V

Transformer to have low flux--low distortion design

Number of secondary windings:

=number of meters to be tested + Wh standard + spares as required

Secondary voltage:

200-400 V

Secondary VA rating:

Max 15 VA per winding

Insulation secondary to secondary:

500V, 50Hz, 60seconds

Primary to secondary ratio accuracy:

0.25%(typical)

Secondary to secondary ratio accuracy:

less than 0.02%

Secondary to secondary phase angle accuracy:

- less than 1 minute

Number of secondary output:

1-100