Product Details

Separation-Type Design Single Phase Energy Meter Test Bench Calibration with 48 Energy Meter

Brand Name GENY
Place of Origin China
Model Number YC1891D

Product Features

Delivery Time:30 days after order confirmed
Certification:ISO 9001
Description: Meters under testing: 1P2W Testing mode: active power, reactive power, cross connected reactive power With current output switch, can calibrate 2 element meter With MSVT, can test single-phase meters with closed links between the current and voltage measuring circuits (I-P links) Simultaneously measure meters with same specifications but different meter constants Automatic positioning rotor mark of disc of mechanical meter, with more efficiency. The meter test system can measure mechanical meter, electronic mechanical meters and electronic meter by ways of automatic, semi-automatic or manual operation. With the protection function of overload, short voltage circuit and open current circuit. The swing together of the scanning heads simplifies the control. Starting test, creeping test, accuracy test, dial test , etc.,  Aluminum alloy material, light and strong and corrosion resistant The testing software with friendly Windows 2000 /XP /7 /8 /10 operation system, includes functional module of all kinds of modern energy meter needed, to reality error test, harmonic test, demand test, influence test etc,.  Specifications:

 

YC1891D-6

YC1891D-12

YC1891D-24

YC1891D-48

Number of meter positions

6

12

24

48

Accuracy

0.05

Power Source

YCS-101-250

YCS-101-600

YCS-101-1200

YCS-101-2500

Standard Meter

SZ01A-K3

MSVT

HJ200GL-6

HJ200GL-12

HJ200GL-24

HJ200GL-48

QCD

D5 series

Scanning Head

YCG-2 series

Voltage

Test voltage output

24V – 288V or customized

Power of the voltage output

100VA

250VA

500VA

1000VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.05% at the final range value

Stability

Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load

Better than 0.01%

Distortion factor

Better than 0.3% for linear resistance load

Harmonics

2nd – 21st free programmable

Current

Test current output

1mA – 100A  or customized,Max.200A

1mA – 100A

Power of the current output

150VA

350VA

750VA

1500VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.05% at the final range value

Stability

Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load

Better than 0.01%

Distortion factor

Better than 0.3% for linear resistance load

Harmonics

2nd – 21st free programmable

Phase angle

Range

0 -- 360°

Resolution

0.01°

Setting accuracy

You May Like

Find Similar Products By Category

You May Like

View More