Eco-friendly Heat Pump Package Unit -Air Cooled Modular Combination

Specifications:

Model   EKAC 220BR1 EKAC 440BR1 EKAC 660BR1 EKAC 880BR1
Unit combination Master unit EKAC220BR1M EKAC220BR1M EKAC220BR1M EKAC220BR1M
slave unit -- EKAC220BR1S 2*EKAC220BR1S 3*EKAC220BR1S
Nominal cooling capacity kW 63 126 189 252
USRT 17.92 35.84 53.76 71.68
×104kcal/h 5.42 10.84 16.26 21.68
Nominal heating capacity kW 68 136 204 272
USRT 19.34 38.68 58.02 77.36
×104kcal/h 5.85 11.7 17.55 23.4
Nominal cooling input power kW 19.0 38 57 76
Nominal heating input power kW 19.8 39.6 59.4 79.2
Power supply   380-415V/3Ph/50Hz
Refrigerant Type   R410A
Control   Electronic expansion valve
Compressor Type   Fully hermetic scroll compressor
Lubricant   Grease (POE-160SZ)
Qty. Set 2 4 6 8
Fan Type   Axia fan with large blade and low noise
Qty. Set 2 4 6 8
Water side heat
exchanger
Type   High efficiency vacuum brazed plate type
Water flow for
cooling
m3/h 10.8 21.6 32.4 43.2
Water flow rate
in heating mode

m3/h
11.7 23.4 35.1 46.8
Water pressure drop kPa 43 43 43 43
Recommended diameter for general inlet/outlet water pipe inch ≥2 ≥3 ≥3 ≥4
Power cable specification Section area of live line
mm2
≥10 ≥35 ≥70 ≥95
Qty. of live lines 3
Section area of null line
mm2
≥4
Qty. of null lines 1
Section area of grounding line
mm2
≥10 ≥16 ≥35 ≥50
Qty. of grounding lines 1
Dimensions L x H mm 2012×1840
Width mm 880 2125 3370 4615
Unit weight Net weight kg 515 1030 1545 2060
Operating weight kg 525 1050 1575 2100


■ Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172m3/(h·kw); outdoor ambient temperature 35°C.Note:

■ Test conditions for nominal heating capacity: outlet water temperature 45°C; water flow: 0.172m3/(h·kW); outdoor dry/web bulb temperature 7°C/6°C.

■ Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y strainer.

■ Main Pipes of combined units need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK does not provide the pipes.

■ Modular units can be formed using the 1 - 16 basic

Contact Supplier

Mr. Rocky sale Manager Chat Now
Telephone
86-769-83660888
Mobile
86-13510311373
Fax
86-769-83622528
Skype
zhoufang@euroklimat.
Address
Euroklimat Industrial Park Zibo,Shandong

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Machinery > Plastic & Rubber Machinery > Plastic Product Making Machinery > Plastic Extruders
Categories