PE sheathed Copper conductor XLPE insulated Electrical cable GB/T12706.1-2002
Product Standard
GB/T12706.1-2002, equivalent to IEC60502
UsageThis product is suitable for use in rated AC voltage(U0/U) 0.6/1kV system transmitting and distributing circuit.
Property for Use It is far better than all property targets of PVC insulated power cable and has overcome the short comings of physical and chemical cross-linkage, and completely reaches or surpasses GB and IEC technical property value. The allowed max .cable conductor work temperature is 90℃;urgent excess work temperature is 130℃for short circuit(5s), max. conductor temperature is 250℃. The environmental temperature for laying cable should be not less than 0℃. If laying under 0℃, the cable should be preheated. The cable bend radius for single core should be not less than 12 times of overall cable diameter; for multi-core cable, not less than 10 times of overall cable diameter. The current-carrying capacity is large and not limited by drop during laying .