IEC standard AMI / AMR smart Single phase Electronic energy meter for residential
Negotiable /Kilogram
Min.Order:1 Kilogram
Hangzhou xili watthour meter manufacture company
Single Phase electric energy meter box / electric enclosure box with SMC material
Electric Three Phase Energy Meter Test Bench with class 0.05 / 0.1 High Accuracy
Energy Meter Components sampling CT current transformer with DC immunity
Four Wire electrical Three Phase energy meter with High Precision , Industrial Use
AV 250V Magnetic latching relay for energy meter components , small volume
Durable PC electricity KWH energy meter box for kilowatt hour meters
Quick Detail:
The XL1000 IEC standard AMI/AMR ready smart Single-phase, Multi-functional Electronic electricity meter is the latest advanced design of Xili metering. This cost-effective meter is equipped with active/reactive measurement, complex tariff functionality and enhanced features like load profiling, anti-tampering, logbook etc. This design is compliant with IEC and MID standards (for European countries). The meters measure active and reactive energy in both directions. Direct connected meters are available for rated current up to 100A.
Description:
The meter allows load profile recording in up to 4 channels and includes various logbooks. Several instantaneous values are available for easier installation diagnostics.
This meter provides a complete multi-configurable billing calendar to respond to all new management needs arising from the deregulated market.
Data communication via the optical port or the serial port (RS485) interface can be done by using either the standard protocol acc. IEC62056-21 (former IEC1107) or COSEM/DLMS.
Applications:
Single-phase 2-wire, direct connected energy meter for residential applications.
Specifications:
Type |
Single-phase 2-wire, direct connected energy meter |
Reference voltage (Un) |
230 Volts AC (other voltages available on request) |
Reference Frequency (Fr) |
50 Hz or 60 Hz |
Extended Operating voltage range |
80%-115% Un |
Basic Current (Ib) |
5A, 10A |
Maximum Current (Imax) |
Up to 100A |
Short-circuit ≤ 10 ms |
30 Imax |
Measuring Accuracy |
Class 1 |
Starting current |
0.4% Ib |
Burden |
≤10VA,1.8W |
Protective Class |
Class II (double insulated) IEC 62052-11 |
Operation temperature rage |
-20℃~+55℃ |
Storage temperature rage |
-25℃~+60℃ |
Life span |
10 years |
Reference standard |
IEC 62052-11; IEC 62053-21 |
Dimension |
186.25x126x56mm |
Competitive Advantage:
Features
• Cost-effective meter
• Easy integration into existing and future reading systems
• Reduced data collection cost because of high data transmission rate
• Less regular intervals necessary to synchronize device clock
• Easy installation
User Benefits
• Voltage Ranges: up to 240V
• Current Ranges: 5 to 60 or 5 to 100A for DC
• Accuracy: Direct connected: Class 1 (IEC 62053-21);Reactive energy: Class 2 (IEC 62053-23)
• Load profile record with up to 4 channels; two logbooks (one certifiable)
• Optical port and serial port (RS485) interface
• Device clock with high accuracy