Features:
The products comply with IEC61643-11, GB18802.1-2011.
The housing is fixed on 35mm electrical guide, and with failure release device inside. As long as SPD become invalid after the breakdown caused by over-heat and overload current, the failure release device will be disengaged from power system automatically with the warning indicator turning from Green (normal) to Red (failure)
SPD
is usually installed in household power distribution boards, telecom
machinery center, computer equipment center, elevator control center,
hospital's surgery and ICU, information equipment, electronic equipment
and in front of control equipment or nearest socket box of control
equipment.
Technical Parameters:
Model number | WPX-MPA20-275/1+N |
Nominal operating voltage (Un) | 220VAC |
Maximum continuous running voltage(Uc) | 275VAC |
Nominal discharge current (In) (8/20us) | 10kA |
Maximum discharge current (Imax) (8/20us) | 20kA |
Voltage protection level up at 1KA(8/20us) | ≤1000V |
UP at 5KA(8/20us) | ≤1400V |
Up at In | ≤1800V |
Response Time | ≤25ns |
Working Temperature & Humidity | -40°C~85°C,≤95%(25°C) |
Install method | DIN 35mm rail |
Indication function | Working indication/malfunction indication /Remote signalling function |
Wire maximum install dimension | ≥25mm² |
Best wire maximum install dimension | 6-25mm² |
Protection mode | L-N,N-PE |
Color | can be customized |
Protection Level | IP20 |
Applications:
1. Low voltage general electricity cabinet and/ or distribution board of buildings.
2. Outdoor electricity cabinet/ distribuition box.
3. Any circumstance need to record the lightning leakage.