ZW32 50 ( 60 ) Hz High Voltage Outdoor electric abb Air blast  Circuit Breakers pdf
Air Circuit Breakers Technical parameter
 

Table 1  Circuit Breaker\'s Main Technical Data

Data

NO

Item

Unit

12kv

1

Rated voltage

kV

12

2

Rated frequency

Hz

50

3

Rated current

A

630/1250

4

Rated short circuit breaking current

kA

20/25

5

Rated peak withstand current

kA

50/63

6

Rated short time withstand current/ lasting time

kA/s

20/4 , 25/4

7

Rated short circuit closing current(peak)

kA

50/63

8

Rated operating sequence

O-0.3s-CO-180s-CO

9

Mechanical life

10000

10

Rated short circuit breaking current breaking times

50

11

1min power frequency withstand current

(wet)

kV

34/36

(dry)

kV

42/49

12

Lightning impulse withstand voltage(peak)

kV

75/85

13

Secondary circuit power frequency withstand voltage (1min)

V

2000

 Table2 Circuit Breaker\'s Main Mechanical Data

NO

Item

Unit

Data

12kv

1

Clearance between contacts

mm

9±1

2

Contact\'s overtravel

mm

2.5±0.5

3

Open speed

m/s

1.4±0.2

4

Closing speed

m/s

0.7±0.2

5

Contact closing jumping time

ms

≤2

6

Pole center distance

mm

340±1.5

7

 Three pole open/close non-simultaneity

ms

≤2

8

Each pole conducting circuit resistance

μΩ

≤70

9

Closing time

ms

25-60

10

Open time

ms

20-60

11

Motor\'s rated power

w

40

ZW32-12 type outdoor high voltage vacuum circuit breaker is three-phase AC,
50(60)Hz outdoor power distribution equipment with the rated voltage of 12kv,
Used to open and close the load current, over load current, and short circuit current in the electric power system. 
Also used to protect and control the circuit in substation, mining and industrial enterprises,
 and frequently used in the operation places such as rural power network. 
 
Air Circuit Breakers Using environmental condition 
A. The altitude above sea level does not over 2, 000 meters; 
B. Surrounding air temperature: -40 ℃ ~+40 ℃ ; 
C. The wind speed is not bigger than 34m/s; 
D. The air filthy should be with in Ⅲ degree
E. Installing places: Not flammable,  the explosion hazard,  chemistry corrode place; 
F. Does not have the regular fierce vibration

Contact Supplier

Mr. Du sale Manager Chat Now
Telephone
86-755-23154925
Mobile
86-13054698745