High Voltage 220V, 85 - 300Vac, 45 - 65Hz Emerson Power Supply Rectifier, R48-1800A
Negotiable /Set
Min.Order:1 Set
Variable 200 - 250 VAC Regulated Power Supply, Power Supply Rectifier R24 - 2200
Emerson 9 -18V, 200 mA Power Supply Rectifier, DC Power Supply PSM - 8
Emerson 840 W Power Supply Rectifier For A / B Power Series Amplifier PS4 - 840
50 V Agilent / HP Power Supply Rectifier / N6761A Precision DC Power Module
Agilent 60 V 20 A 300 W Power Supply Rectifier, DC Power Supply N6754A
Cisco Emerson M500d Monitoring Module, 19v - 60v Power Supply Rectifier
High Voltage 220V, 85 - 300Vac, 45 - 65Hz Emerson Telecom Power Supplies, R48-1800A
R48-1800A system features
The rectifier module uses active power factor compensation technology, power factor value of 0.99.
Wide AC input voltage of the normal operating range to 85V ~~ 300V.
The rectifier module the comprehensive soft switch technology, rated up to 91% efficiency. The system efficiency up to 88%. Rectifier module ultra low radiation. Rectifier module is able to meet the advanced EMC design, CE, NEBS, YD/T983 domestic and international standard requirements. The rectifier conduction and radiation can reach Classl B requirements.
Rectifier module safety design meets UL, CE, NEBS standards.
Rectifier module hot swap technology, plug-and-play with no damage, replacement time less than 1min.
Rectifier module output overvoltage hardware protection and output overvoltage software protection. Software overvoltage protection, there are two options: one-off pressure lock mode, secondary overvoltage locked mode.
Perfect battery management. Low battery voltage protection function and load power to achieve temperature compensation, automatic voltage regulator, stepless current limit, the battery capacity is calculated online battery test function.
Historical alarm records can record 200; 10 group battery test data can be recorded.
Network design, multiple communication interface provides one RS232 interface, Modem, dry contact, flexible networking, remote monitoring, unattended.
Model Number |
R48-1800A |
Manufacturer |
Emerson |
Environmental conditions |
Operating temperature -5 ~ 40 ℃ |
Storage temperature |
-40 ~ 70 ℃ |
Relative Humidity |
5 ~ 95% RH |
Altitude |
≤ 2000m (more than derating) |
Rated input voltage |
220V |
Input voltage range |
85 ~ 300Vac |
AC input voltage frequency |
45 ~ 65Hz |
Maximum input current |
≤ 40A (170V input) |
Power Factor |
≥ 0.99 |
DC output voltage of the DC output |
42.2 ~ 57.6Vdc |
Output DC current |
0 ~ 300A |
regulation accuracy |
≤ 1% |
efficiency |
≥ 88% |
The peak-to-peak noise voltage |
≤ 200mV (0 ~ 20MHz) |
Tel Weighted noise voltage |
≤ 2mV (300 ~ 3400Hz) |
Broadband noise voltage |
≤ 100mV (3.4kHz ~ 150kHz); ≤ 30mV (150 kHz ~ 30MHz) |
Discrete noise |
≤ 5mV (3.4kHz ~ 150kHz); ≤ 3mV (150kHz ~ 200kHz); ≤ 1mV (0.5MHz ~ 30MHz) |
Dimensions |
87.9mm (high) x 85.3mm (width) × 272mm (D) |
The AC distribution Lightning II / C-level lightning two AC input open space
Specifications:
2 x 100A/3P single AC input, AC input specifications 1 × 63A/4P open space
AC output empty open specifications: 1 × 16A/3P, 3 × 16A/1P user exchanges
the the output empty open specifications: 1 × 16A/3P 1 × 16A/1P
DC power distribution Lightning DC side lightning two battery input fuse: 2 × 250A NT1
Load output 12 road load output, the total load current ≤ 200A. Where:
1. 6-way electrical tributary load, including:
5 × 100A (FUSE), 1 × 63A/1P (MCB)
2. Battery protection, electrical tribut