High Accuracy Three Phase Reference Standard Meter For Energy Meter Test

High Accuracy Three Phase Reference Standard Meter For Energy Meter Test

Negotiable /Carton

Min.Order:1 Carton

Supply Ability:
0 Carton / Cartons per Month
Payment Terms:
T/T L/C D/P D/A
Delivery Detail:
7 days

Quick Details View All >

Brand Name:
KRE
Place of Origin:
China
Model Number:
KE9302

Guangzhou Kingrise Enterprises Co.,Ltd

Business Type: Trading Company
Main Products: Energy Meter Test Bench

Product Details

Delivery Time:1-2 month
Display Type: Large screen color LCD display Phase: Three Phase Accuracy Class: ± 0.05% (40V – 500V) Name: Reference standard meter, standard energy meter, reference energy meter Voltage range : 10V – 500V Current range1mA – 120A Operating Temperature: -10°C -- +40°C Dimensions: 445mm×260mm×480mm

High Accuracy Three Phase Reference Standard Meter For Energy Meter Test

KE9302 three phase reference standard meter is used as the power standard for the electric power departments, meter manufacturing companies and institutes of metrology; it is fit for all of the three phase energy meters test system with different modes.

Highlight: High speed DSP and high accuracy ADC to make sure the quick and accurate measurement Large screen color LCD display rich measuring info Touch screen design, simple and easy operation Completely independent measuring channel, greatly reduce the mutual interference User-defined 3 channel pulse output, flexible configuration. 3 channel pulse input could test 3 meters simultaneously Various interfaces (including RS-232, USB, Ethernet, etc) to connect to PC or other devices. Measuring data could be saved, browsing and displayed. Main specifications:

Voltage measurement

Voltage range

10V – 500V

Accuracy

±0.05% (40V – 500V)

Harmonics

2nd- 51st

Current measurement

Current range

1mA – 120A

Accuracy

±0.05% (0.01A – 120A)

Harmonics

2nd- 51st

Power measurement

Active power

±0.05% (0.01A – 120A)

Reactive power

±0.05% (0.01A – 120A)

Apparent power

±0.05% (0.01A – 120A)

Energy measurement

Active energy

±0.05% (0.01A – 120A)

Reactive energy

±0.05% (0.01A – 120A)

Apparent energy

±0.05% (0.01A – 120A)

Phase measurement

Phase range

0° -- 360°

Accuracy

±0.001°

Frequency measurement

Frequency range

45Hz-- 65Hz

Accuracy

±0.001Hz

Pulse output

High frequency output(CH)

Defined by users

Low frequency output(CL)

CH / 10000

Output channel

3

Pulse input

Input channel

3

Input frequency

Max. 1MHz

Others

Power supply

220V±10%  50/60Hz±2Hz

Temperature

-10°C -- +40°C

Humidity

45% -- 75%RH

Dimension

445mm×260mm×480mm

Weight

25kg

Contact Supplier

Betty Li Chat Now
Telephone
86-020-62220181
Mobile
86-13570974148
Fax
86-020-62220182
Address
Rm 210, No 69 Guangpu Rd(W), Luogang Dist Ji'nan,Shandong

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Electrical Equipment & Supplies > Batteries > Primary & Dry Batteries
Categories
Hi~