fixed combustible gas detecting transmitter
Negotiable /Unit
Min.Order:1 Unit
Henan Chicheng Electronics Co.,Ltd
QB2000T is a fixed combustible gas detecting transmitter.Whichprovides 4-20 mA output and RS485 ModBus RTU outputproportional to the gas concentrationwith electrochemical sensor, which is flexible, durable, swift and etc. and can be directly connected with DCS systems.It has been widely used in petrol, chemistry, metallurgy, artifice, gas transportation, biological medicine and water procession etc to test multi-gas, such as flammable gas and toxic gas O2,H2S,CO,HCN,NO2,SO2,NH3,HCL,CL2,H2.
Characteristics:
◆Sensor types:catalytic combustion sensor.
◆4-20mA analog output(3+ channel) for direct communication to DCS system and RS485 ModBusoutput
◆Sensormodule design on -spot replacement s and automatically distinguish sensor fault and current display fault simultaneously.
◆LED Display(LCD optional)
◆Password verification for repeat operation, avoid fault operations.
◆-40~+70℃ following compensationfor accurate detecting.
◆Second grade visual alarms on-site and Relay(connected with audible/visual alarms or drive exhaust device).
◆User-selectable alarm setpoint(s).
Environment Parameter
|
Environment temperature:-20℃~+60℃
|
Relative humidity ≤90%R.H.
|
|
Technical Parameters
|
Working voltage: 16~30VDC
|
Working current: flammable gas is 120mA, others ≤50 mA
|
|
Output signal: 4~20mA standard signal two wire type output (QB-01T three wire type)
|
|
Sensor
|
electrochemical sensor; QB-01T is catalytic combustion type
|
Respond Time
|
T90 less than 30 seconds
|
Exterior Structure
|
Weight ≤900g
|
Fixing Parameters
|
Fixing type: wall-mounted type
|
Transition cable: two core shield cable (flammable gas uses three core shield cable), section 2×1.5mm2, external diameter Ā10mm
|
|
Transferring distant ≤1000m
|
|
Anti-explosion Class
|
Exd IICT6(used for explosion proofing);ExiaIICT4(used for intrinsic safety type)
|
Protection Class
|
IP66
|