380V, 600V 60HZ 4 - 20mA 0.2% Automation PRO DU31 DC Electrical Voltage Transducer
Negotiable /Piece
Min.Order:1 Piece
Shenzhen Artel Technology Co.,Ltd
DIN 35mm Rail 90%RH 50HZ, 60HZ PRO DI31 DC Electrical Current Transducer, ISO 9001
LCD Custom 1 Channel 800A, 50Hz Programmable M60 Protection Controller / Motor Protection Relay
7 Channels 250A 380VAC Flexible full - Ccale Motor Protection Relay, controller With Remote Communic
Programmable Recording LCD 5A Motor Protection Relay, Controller With Automatic Inspection
200A Remote Communication Low - Voltage Overload M60 Protection Controller / Motor Protection Relay
LCD Wireless Temperature And Humidity Detection System / Temperature Humidity Data Logger ARZ-1
380V, 600V 60HZ 4 - 20mA ±0.2% Automation PRO DU31 DC Electrical Voltage Transducer
1. Product Description
Pro Series Transducers for Electrical Quantities, fundamental devices for process automation. All our
instruments fulfill all important requirements and regulations concerning electromagnetic compatibility
and safe isolation (IEC688-1992 standard and GB/T 13850-1998 standard). The devices have been
developed, manufactured and tested in accordance with Quality Assurance System ISO 9001.
2. Technical Specification
Accuracy: Class0.2,0.5
Auxiliary Power Supply: 85V~265VDC/AC 24V~80VDC/AC
Stability: Annual Change Rate ≤±0.2%
Input Overload Capacity:
Continuous Overload Capacity ≤1.5X
Transient Overload Capacity Voltage Limit≤3X Current Limit≤30X
Output:
Constant Voltage Output, Load Resistor Rext≥250Ω
Constant Current Output, Load Resistor Rext≤500Ω
Alternating Wave: ≤18mV(Peak-Peak)
Response Time: ≤300ms
Striking Voltage: ≤2.5kV
Operating Temperature: -10℃~+55℃
Storage Temperature: -40℃~+85℃
Relative Humidity of Annual Mean: ≤90%RH
Installation: DIN 35mm Rail
Size: 35mm×69mm×110mm
Guaranty Period: 2 years
3. Technical Data
Input: 100V, 220V, 380V, 600V
Output: 4-20mA, 4-12-20mA, 0-20mA, 0-10mA, 0-1mA, 0-5V, 0-10V
Frequency: 50HZ, 60HZ
4. Wiring Diagram