Product Details

JB3855 - 1996 VS1 Rated Short -Circuit 4s Indoor 12kV generator Vacuum air Circuit Breaker

Brand Name ELECS
Place of Origin China
Model Number VS1

Product Features

Delivery Time:30 Days
Certification:CE, QS, CCC

JB3855 - 1996 VS1 Rated Short -Circuit 4s Indoor 12kV generator Vacuum air Circuit Breaker

Main specifications and technical parameters(Refer to Tab 1)

Tab 1

No

Item

Unit

Technical data

1. 

Rated voltage

kV

12

2. 

Rated short-time 

power frequency withstand voltage

(1min)

42

3. 

Rated lightning

impulse withstand voltage (peak value)

75

4. 

Rated Frequency

Hz

50

5. 

Rated current

A

630

1250

630  1250 1600  2000

2500  3150

1250 1600

2000  2500 

3150  4000*

6. 

Rated short circuit breaking current

kA

25

31.5

40

7. 

Rated short time withstand current

25

31.5

40

8. 

Rated short-circuit duration

s

4

9. 

Rated peak value withstand current

kA

63

80

100

10. 

Rated short-circuit closing current (peak value)

63

80

100

11. 

Secondary circuit power frequency

withstand voltage(1 min)

V

2000

12. 

Rated single/ back-to-back capacitor bank

breaking current

A

630/400 (40 kA for 800/400)

13. 

Rated capacitor bank making rush

current

kA

12.5(frequency 

no more than 1000Hz)

14. 

Opening time

ms

20~50

15. 

Closing time

35~70

16. 

Mechanical life

Time

10000   30000   60000

17. 

Breaking times at rated short-circuit current

Time

50 (40 kA for 30)

18. 

Permissible wear accumulated thickness

of moving and fixed contact

mm