GAV8A
Negotiable /Set
Min.Order:1 Set
Commonly used name: AVR
Features:
This product uses the high quality resin casting, the PVC outer covering;
Built-in against excitation protection circuit;
When built-in engine revolution drop output voltage along with it drop frequency protection circuit;
Smallest remaining voltage: 10V ;
The power module uses American International the Rectifier(IR) Corporation product, the quality confidence guarantee; Built-in industrial used input fuse
Model NO. GAV8A
Sensing Input Voltage 190~264 VAC 2 phase or 1 phase Frequency 50/60 Hz selectable
Power Input(PMG) Voltage120 VAC 3 phase 3 wire Current 8A / phase Frequency 100~120 Hz nominal
Output Voltage Max. 120 VDC Current Continuous 4A, Intermittent 7A for 60 sec.Resistance Min. 15 Ω
Voltage Regulation < ±1% RMS (with 4% engine governing)
Voltage Build-up Residual volts at AVR terminal > 5 VAC
External Volts Adjustment ±10% with 5 K 1 watt trimmer
Unit Power Dissipation Max. 18 watt
Thermal Drift 0.05% per °C change in AVR ambient
Soft Start Ramp Time 0.4~4 sec.
Analogue Input Max. input ±5 VDC Sensitivity 1V for 5% generator volts
Input Resistance 1 K Ohm
Droop Input Burden 10 Ohm Max. Sensitivity 0.22A for 5% droop (PF=0)
Max. Input 0.33A
Under Frequency Protection
(Factory Setting) Set point 95% Hz
Slope 100~300% down to 30 Hz
Max. Dwell 20% volts/sec. recovery
Current Limit Input Burden 10 Ohm
Sensitivity range 0.5~1A
Over Voltage Detector Input Set point 300V
Time delay 1 sec. (fixed)
CB trip coil volts 10~30 VDC / 0.5 Amp
Over Excitation Protection Set point 120 VDC
Time delay 8~15 sec.
Environment Operating Temperature : -40~70 °C
Storage Temperature : -40~85 °C
Relative Humidity : Maximum 95%
Vibration : 3.3G @ 100~2 KHz
AVR Controls Functions VOLT : Output Voltage Adjustment
STAB : Stability Adjustment
UFRO : UFRO Knee Point Set
DROOP : To Set the Droop to 5% at PF=0
TRIM : To Optimize Analogue Input Sensitivity
EXC : Over Excitation Trip Level Set
DIP : Hz Related Voltage DIP Set
DWELL : Hz Related Recovery Time Set
I LIMIT : Stator Current Limit Set
OVER V : Over Voltage Trip Level Set
RAMP : No Load Voltage Ramp Set Time
RMS : Root Mean Square of Generator
Dimensions 181.0 (L) x 92.0 (W) x 56 (H) mm
Weight 530 g ±2%