Product Details

Hot sale eco air to water heat pumps efficiency monobloc

Brand Name HISEER
Place of Origin China
Model Number AW15-DNNNE

Product Features

Delivery Time:10-15 days after TT payment
Certification:CE EN14511

Hot sale eco air to water heat pumps efficiency monobloc

AW15-DNNNE, Air-source heat pump, often used in moderate climates, use the difference between outdoor air temperatures and indoor air temperatures to cool and heat your home, at the same time to supply domestic hot water.

HISEER AW15-DNNNE, galvanized sheet, high efficiency air to water heat pump, 380-415V/3/50Hz, R410a refrigeration, designed and tested by EN14511, approved by TUV china branch, adopt the following world famous parts:
* SWEP or GEA plate type heat exchanger
* Siemens controller
* Daikin scroll compressor
* Schneider A/C contactor
* Emersion thermal expansion valve
* Emersion dry filter
*Soft start is standard part

How does a air source heat pump work?
An air source heat pump is made up of three main components - an evaporator coil, a compressor, and a heat exchanger.

The evaporator coil is fitted to the outside of an external wall. It absorbs heat from the outside air. The compressor pushes the refrigerant gas through the system compressing it until it is at the desired temperature (typically up to 35-40 degrees Celcius). The hot refrigerant then passes through the heat exchanger where the heat from the refrigerant is transferred to water or air.

the operation of a heat pump can be reversed and used to cool down the air in a building by radiating it outside - behaving in exactly the same way as a refrigerator.

Coefficient of performance

ASHPs supply more energy than they consume. By extracting heat from the surrounding air, the heat energy released can be up to 3 times the energy required to power the equipment.

AW15-DNNNE technical data

AIR TO WATER HEAT PUMP

AW15-DNNNE

Heat output/Power consumption at 7/35℃

kW

16.0/4.3

Heat output/Power consumption at 7/45℃

kW

15.4/5.0

Heat output/Power consumption at 7/55℃

kW

14.8/6.2

Heat output/Power consumption at 2/35℃

kW

13.8/4.3

Heat output/Power consumption at 2/45℃

kW

13.3/5.0

Heat output/Power consumption at -7/35℃

kW

10.3/4.4

Heat output/Power consumption at -7/45℃

kW

10.2/5.1

Starting current 

A

56

Power

380-415V/3PH/50Hz

Compressor

HITACHI scroll

Condenser

Brazed plate heat exchanger

Nominal flow heating medium

l/s

0.76

Internal pressure drop at nominal flow

kPa

22

Air flow

m3/h

5000

Nominal output fan

W

300

Max outgoing heating medium temperature

55℃

Dimensions(HxWxD)

mm

1075x1105x505

Pipe connector

You May Like

Find Similar Products By Category

You May Like

View More
Chat Now Contact Now