Product Details
Model No.:
Product Origin:
Brand Name:
Price Terms:
Payment Terms:
Certification:
Description:Specifications:
1) Name: 1 pole definite purpose contactor
2) Model number: HLC-1N
3) Contact:
a) Arrangements: 1 pole N.O. without shunt
b) Structure: double make contacts
c) Materials: silver cadmium oxide (10% to 30Amp 13% 40Amp)
d) Max. loading rating: see contact rating chart
4) Coil:
a) Coil voltage: 50/60Hz, see coil rating chart
b) Nominal resistance: see coil rating chart
c) Nominal inrush power: 5VA@60Hz, 6VA@50Hz
d) Coil temperature rise: 65oC max.
e) Class of insulation: 130oC class B
5) Operation:
a) Must operate voltage: 85% of nominal coil valtage or less
(24VAC=75% or less)
b) Must release voltage: 10% to 60% of operate voltage
c) Initial operate time: 20ms typical
d) Initial release time: 10ms typical
e) Bounce time: 0 to 10 ms typical
6) Environment:
a) Temperature range: storage and operating -40 - 65oC
7) Initial dielectric strength:
a) Between contacts and coil: 2,500VAC
b) Between poles: 2,500VAC
c) Between open contacts: 2,500VAC
8) Mechanical data (power pole termination: wire size, tightening torque):
a) #10-32 screw: 16 - 8 AWG, 22Ibf.-in.(2.49Nm)
b) Box lug: 14 - 4 AWG, 40Ibf. -in. (4.52 Nm)
9) Coil termination: dual 0.250 quick connects (6.35mm)
10) Unit weight without optional cover: 7oz (200g/m)
11) Life expectancy: depends upon duty cycle, load, and environmental
conditionals
12) Mechanical life:
a) Design requirement AR1780 = 500,000 operations
b) Min test requirement = 1,000,000 operations at 60 operations per
minute, 50% Duty cycle, 150 F and 110% of nominal coil volatage
13) Electrical life test results:
a) 40 and 50 RLA (resistive load)
b) 250,000 operations make, carry and break 100% pf. 600VAC 30 FLA rated
c) 200,000 operations make LRA 40 to 50% pf., break 125% FLA 75 to 80%
pf.@240VAC
d) 250,000 operations make, carry, break 75 to 80% pf.@240VAC
e) 250,000 operations make, carry, break 75 to 80% pf.@600VAC
40 FLA rated
f) 100,000 operations make LRA 40 to 50% pf., break 125% FLA 75 to 80%
pf.@240VAC
g) 250,000 operations make, carry, break 75 to 80%pf.@240VAC
h) 300,000 operations make, carry, break 75 to 80%pf.@600VAC