MEGATRO 1000KV 10GB2-SZ1 double circuit Transmission tower
USD $920 - $960 /Ton
Min.Order:1 Ton
Qingdao Megatro Holding Co., Ltd.
MEGATRO 1000KV 10GB2-SZ1 double circuit Transmission tower
This photo refers to our 1000KV 10GB2-SZ1 double circuit Transmission tower, it is widely used in our Chinese market. Some of technical features of this tower as follow:
1 climate condition
Item | Temperature (℃) | Wind speed (m/s) | Ice thickness (mm) |
Max. temperature | 40 | 0 | 0 |
Mini. temperature | -15 | 0 | 0 |
Ice thickness | -5 | 10 | 10 |
Basic wind speed | -5 | 30 | 0 |
Installation condition | -5 | 10 | 0 |
Annual temperature | 15 | 10 | 0 |
Lightning overvoltage | 15 | 15 | 0 |
Operation overvoltage | 15 | 18 | 0 |
2 Technical specification of conductor and OPGW
Item | Conductor | OPGW | |
JL/G1A-630/45 | JLB20A-240 | ||
construction | AL | 45×3.76 | 59.69 |
Steel(Al wrap steel ) | 45×4.22 | 179.07 | |
Cross-section (mm2) | Al | 630.00 | 238.76 |
Steel | 43.39 | 20.01 | |
Total | 674.00 | 1595.50 | |
Diameter | 33.80 | 147200 | |
Length mass (kg/km) | 2079.20 | 13.0×10-6 | |
Elastic module (MPa) | 63000 | 147200 | |
coefficient of linear expansion (1/℃) | 20.9×10-6 | 13.0×10-6 | |
Rated broken (N) | 150450 | 260010 |
3 tower design data
Tower type | Nominal Height (mm) | Horizontal span (m) | Vertical Span (m) | Angle º | Nominal height tower weight Kg |
10GB2-SZ1 | 54 | 400 | 500 | 0 | 111569 |
4 type and force of conductor and OPGW
Power voltage |
1000KV | Conductor type | 8×JL/ GIA-630/45 | Max. operation Tension force (KN/phase) |
457.368 |
Un-balance Stress value(%) |
10 |
OPGW Type | JLB20A-240 | Max. operation Tension force (KN/pc) | 68.424 | Un-balance Stress value(%) | 20
|
5 Operation data
Item
| Horizontal span (m) | Vertical Span (m) | Representative Span (m) | Angle º | Height (m) | KV |
data | 400 | 500 | 400 | 0 | 54 | 0.85 |
6 loading data
Site condition | Normal operation condition | Accident condition | Installation condition | Uneven icing | |||||
Basic wind speed | Ice | Mini. temperature | Non- broken | broken | |||||
Climate condition (t/v/b) | -5/30/0 | -5/10/10 | -40/0/0 | -5/0/10 | -5/0/10 | -15/10/0 | -5/10/10 | ||
Horizontal loading | conductor | 92441 | 20081 | - | - | - | 9638 | 20081- | |
Insulator Power fitting | 8640 | 1440 | - | - | - | 1440 | 1440- | ||
OPGW | 9051 | 2253 | - | - | - | 861 | 2253- | ||
conductor | 81560 | 130160 | 81560 | 130160 | 130160 | 81560 | 130160- | ||
Vertical loading
| Insulator Power fitting | ||||||||
OPGW | 7825 | 11985 | 7825 | 11985 | 11985 | 7825 | 119825- | ||
Stress force | conductor | One side | - | -- | - | 91474 | 91474 | - | -- |
The other side | - | -- | - | 91474 | 0 | - | -- | ||
Stress differences | - | -- | -- | 0 | 91474 | - | 45737 | ||
Stress force | OPGW
OPGW | One side | - | -- | 68424 | 68424 | - | -- | |
The other side | - | -- | 68424 | 0 | - | -- | |||
Stress differences | - | -- | 0 | 68424 | - | 13685 |
7 Foundation distance size
Nominal Height (m) | Foundation distance (mm) | Anchor bolt | |||
Front distance | Side distance | Type and quantity | Distance /radius (mm) | Material | |
45 | 15860 | 15860 |
12×M52
| 396 |
Chinese type 35 steel |
48 | 16532 | 16532 | |||
51 | 17204 | 17204 | 410 | ||
54 | 17876 | 17876 | |||
57 | 18548 | 18548 | 420.5 | ||
60 | 19220 | 19220 |
8 Foundation force
Nominal Height (m) | Tx | Ty | T | Nx | Ny | N |
45 | 338 | 313 | 2655 | 436 | 409 | 3492 |
48 | 346 | 325 | 2719 | 449 | 426 | 3577 |
51 | 353 | 332 | 2765 | 459 | 436 | 3647 |
54 | 365 | 338 | 2803 | 457 | 442 | 3728 |
57 | 371 | 343 | 2846 | 475 | 450 | 3795 |
60 | 379 | 359 | 2894 | 494 | 475 | 3865 |