LiFePO4 battery 12V110 for energy storage
USD $300 - $350 /Set
Min.Order:4 Sets
Ocell New Energy Technology Co., Ltd.
LiFePO4 Battery12V110
1) Ultra-long life cycle vs SLA battery
2) Lighter weight and Smaller size vs SLA battery
3) Stable output vs SLA battery
4) Fast chaging & discharging is available vs SLA battery
5) Enviromental friendly
Specification
Item | Comments |
Battery module | 110Ahr or 1408Whr (316PCS IFR18650EC-1.5Ah cells in a 4S79P configuration. Or 136PCS IFR26650EC-3.3Ah cells in a 4S34P configuration ) |
Approx. Dimension | 260 mm x 158mm x 246 mm (L*W*H) |
Approx. Weight | 15.1kg |
Nominal voltage | 12.8V |
Maximum voltage | 14.6V |
Minimum voltage | 10.0V |
Nominal load current | 150A max. continuous current @ 23° C |
Peak load current | 300A max for 30 sec @ 23° C |
Charge protection | When the Battery modules are charged to full, they will communicate with BMU, and the BMU has the capability to turn off the charger or open the main contactor. The battery module itself does not have any switch to disconnect the charger. |
Balancing | The intra-module balancing circuit is used to compensate slight capacity imbalance among the four cell blocks within a battery module. The inter-module balancing circuit is used to compensate slight capacity imbalance between different battery modules in series connection. |
State of Charge Measurement | Individual cell block voltage and charge/discharge current will be used to monitor the state of charge (SOC) of the battery module. The estimated capacity used for the calculations will be adjusted to meet the capacity of the lowest capacity cell block when the battery system is fully cycled. The state of charge will be adjusted for normal self discharge of the battery system when the unit is not on charge. |
RS-485 Communication Uplink | RS-485 Communications will be used to communicate with the Battery Management Unit (BMU) or connection to other battery Modules. |
RS-485 Communication Downlink | RS-485 Communication connection from Downstream battery module. |
RS-485 insulation voltage rating | 1414V , 5000V rms for 1 minute |
Status LED | A Dual LED on module to indicate working status. One is green and the other one is red. Blinking of the green LED indicates that the module is working properly. Blinking of the red LED indicates that the module has failure and needs service. |