cabinet cooling air conditioners
USD $100 - $5,000 /Set
Min.Order:1 Set
Xiamen AIR-ERV Technology Co., Ltd.
Product Description
Cabinet heat exchangers is specially designed for telecom cabinet and electric cabinet, in order to remove heat generated by electric equipment (such as PLC, converter machine, relay, driving system, telecom module); It provides the electric cabinet with an environment of ideal temperature and humidity, isolating dust and moisture. Product side mount on indoor and outdoor cabinet. By using air conditioner series can prolong lifetime of the electric products and greatly improving the system’s reliability
Application range
outdoor communication base stations, 3G base stations, communication cabinet, power stations, outdoor media, Network management centre ,control system, mobile base station and base station equipment rooms etc.
Features
1. Unique heat exchanger core (counter flow or cross flow), high heat exchange rate
2. Airtight circulation cooling system,separated indoor and ourdoor air,avoid pollution from ourdoor air,keep cabinet dry and clean.
3. Ultra-thin structure design, diversiform installation ways, allowed side,door and top installation.
4. High quality components, ensure stable and reliable operation.
5. Compact appearance,convenient installation.
6. Less running parts, long service life and maintenance free.
7. Intelligent control, Multilevel heat transfer.
8 . DC,AC version available for various application
9. High IP,reach to IP65, low energy consumption.
DC vension vs. AC version heat exchanger
1. DC version is recommended comparing AC version HEX since it is PWM Speed controlled and much more efficiency.
2. DC version is vey suitable especially for residential area since the noise can be controlled under acceptable level.
3. DC version can provide emergency cooling when mains loss.
Technical parameter
Model | ||||||||
Parameter | Unit | HEU C060 | HEU C080 | HEU C100 | HEU C120 | HEU C150 | HEU C180 | |
Heat transfer | W/K | 60 | 80 | 100 | 120 | 150 | 180 | |
Air volume | m3//h | 350 | 450 | 600 | 700 | 900 | 1100 | |
Excess pressure | Pa | Greater than 100 | ||||||
Power | W DC-48V | 80 | 120 | 160 | 200 | 200 | 270 | |
W AC-220V | 90 | 145 | 180 | 220 | 220 | 300 | ||
Voltage | V | DC 48V AC 220V | ||||||
Temperature range | °C | Negative 40 to 70 °C 0 to 100% RH | ||||||
Noise | Db(A) | 48 | 50 | 52 | 54 | 55 | 56 | |
Demension | mm | 150*380*800 | 150*450*950 | 190*450*1150 | 190*450*1150 | 240*450*1300 | 240*600*1350 | |
Weight | Kg | 20 | 30 | 39 | 39 | 40 | 48 | |
IP protection class | Greater or equal IP55 | |||||||