FN510 Field Wireless Multi-Function Module
Negotiable /Unit
Min.Order:1 Unit
Xian Wellwork Industrial Co., Ltd.
Product Information
FN510 Field Wireless Multi-Function Module
Field Wireless Multi-Function Module with “Field Wireless Communication Module FN110” is connectable with a field wireless network as a field wireless device. This product acquires sensor data from a connected sensor and transmits it to a field wireless network through FN110. Refer to General Specifications of “Field Wireless Communication Module FN110” for an overview and detailed information.
• Various Input / Output functions:
Analog input, digital input/output or pulse input are selectable.
• Connect various sensor to the field wireless network:
This product transmits sensor value acquired from a 4-20 mA analog device to the host system via field wireless network.
• Installation flexibility:
Cable elimination allows installing a device at locations where it was previously either inaccessible or cost-prohibitive because of cable management and cost.
• Small and lightweight housing with LCD:
This product has a small and lightweight housing with a built-in LCD that displays the process data and communication status.
Specifications
Power Supply Specifications | Battery | Dedicated battery pack Rated voltage: 7.2 V Rated capacity: 19 Ah Battery Pack:2x primary lithium-thionyl chloride batteries With battery case (batteries sold separately) |
Performance Specifications | Update Period | 1 to 3600 s selectable* *: When using the digital output, more than 2 s is accepted. |
Battery Characteristics | Typical battery life when using analog input or digital input is 10 years* 1 or 7 years* 2 and when using digital output with always on is 3 years* 3 or 2 years* 1 in the following conditions.* 4 • Ambient temperature: 23 ±2°C • Device role: IO mode • LCD display: off *1: Update period: 10 s *2: Update period: 5 s *3: Update period : 30 s *4: Environmental condition such as vibration and the type of connected device may affect the battery life. | |
Functional Specifications | Input | See Table 1. |
Power Supply | Power supply to the FN110 Supply voltage: 3.5 V Supply current: 50 mA | |
Installation Environment | Ambient Temperature Limits | Operating: -40 to 85°C (attitude up to 3000 m) -30 to 80°C (LCD visible range) |
Regulatory Compliance Statements | EMC Conformity Standards | EN61326-1 Class A Table 2 (For use in industrial locations), EN55011 Class A |
Degrees of Protection | IP66 rating applies when the connector is properly tightened. | |
Explosion-Proof Types | TIIS, FM (United States or Canada), ATEX, IECEx (approvals under pending) | |
Physical Specifications | Weight | 500 g (without mounting bracket, clamp, and battery) |
Table 1. Input / Output Function Summary
*1: The input channels are non-isolated and share one common ground.
*2: Do not apply a voltage to a DI or PULSE from the outside.
*3: The digital output terminal is configured as open-drain. The voltage and current applied to a digital output terminal should be within the specified range.
*4: Minimum time required to detect an eternal contact becomes off.