Wholesale Carbon Monoxide Transducer
Negotiable /Piece
Min.Order:10 Pieces
Tongdy Sensing Technology Corporation (Beijing)
Wholesale Carbon Monoxide Transducer
Features
u Special used to real-time detect CO2 level in air ducts.
u NDIR infrared CO2 sensor inside with Self-Calibration and up to 15 years lifetime
u High accuracy humidity and temperature detection&display optional
u With LCD or without LCD selectable
u Providing one dry contact output with presetting the setpoint
u Modbus RS485 communication interface optional
u Wireless of ZigBee protocol optional
u Smart structure with easier wire connection through the external pipe
u Provide four types: wall mounted, duct mounted, split and plug & play
u For plug & play type, special design a photosensor inside to detect
day/night and change the working mode of the CO2 generator
u For duct probe type, special the 180° rotatable fastness position of the
probe can be used in two directions of air flow.
u Replaceable filter in the probe and extendable probe length
u Design the convenient and easier buttons for operation
u
Duct probe mounted |
CE-Approval
Split controller and sensor |
Specifications
CO2 Sensor | Non-Dispersive Infrared Detector (NDIR) | |
Measurement Range | 0~2,000ppm (default) 0~5,000ppm (preset) | |
Accuracy | ±40ppm + 3% of reading @22°C(72°F) | |
Stability | <2% of full scale over the life of the sensor | |
Calibration | Self-calibration system | |
Response Time | <5 minutes for 90% step change at low duct speed | |
Non-linearity | <1% of full scale @22°C(72°F) | |
Duct Air Velocity | 0~450m/min | |
Pressure Dependence | 0.135% of reading per mm Hg | |
Warm up time | 2 hours (first time) 2 minutes (operation) | |
Split CO2 sensor | 2 meter cable connection between the senor and the controller | |
Temperature & Humidity Detection&Display (optional) | Temperature | Relative Humidity |
Sensing element: | Band-gap-senor | Capacitive humidity sensor |
Measuring range | -20°C~60°C | 0 -100%RH |
Accuracy | ±0.5°C (20~40°C) | ±4.5%RH (25°C, 15%-85%RH) |
Display resolution | 0.1°C | 0.1%RH |
Stability | ±0.1°Cper year | ±1%RH per year |
General Data |
| |
Power supply | 24VAC/24VDC or 100VAC~240VAC | |
Consumption | 1.8 W max. ; 1.0 W avg. | |
LCD display | Display CO2 measurement or CO2 + temperature& humidity measurements | |
Dry contact output (optional) | 1xdry contact output for CO2 Max. 5A (100~240VAC/30VDC)rated switch contact | |
Plug& play type | Just for 100VAC~240VAC power supply with European or American power plug and power connector to the CO2 generator | |
Modbus RS485 Interface (optional) | 19200bps, 15KV antistatic protection. | |
Wireless module (optional) | ZigBee 2.4G short distance wireless communication | |
Operation conditions | -0°C~50°C(32~122°F); 0~99%RH, non condensing | |
Storage conditions | 10~50°C(-40~158°F)/ 20~60%RH | |
Net weight | 280g | |
IP class | IP30 | |
Standard Approval | CE-Approval |
Typical Applications
u In office and residence areas to detect CO2 level
u Ventilation control
u In BAS to detect the CO2 and the data transmittance
u For greenhouse and plant bin
u For CO2 laboratory