Ceramic Station Post Insulator ANSI TR205, TR208, TR210, TR214, TR216
About the Porcelain Station Post Insulator
Porcelain station post insulators according to IEC, ANSI and other standards are used in substations and related switching equipment. They are produced in single piece up to 2300 mm and can operate voltages up to 1100KV in stacked configuration. Post insulators are subjected to compression, cantilever and torsional loads during service.
Advantages of porcelain station post insulator
1. This porcelain station post insulator is produced with advanced isostatic pressing dry-forming technology
2. This porcelain post insulator has high bending strength load,which is enable to keep stability under sever natual circumstance.
3. The surface of this porcelain station post insulator has perfect glaze, which can be made into light grey or brown according to your requirement.
Pecifications
1.Certificated by IEC ANSI GB ISO9001
2.We can design and produce according to the drawings.
3.We supply insulators with reliable quality reasonable price and good service.
4.We've attended 2007 Hannover exhibition, India electricity 2008 exhibition,2008 Hannover exhibition,2009 and 2010 Dubai Middle East electricity exhibition
ANSI CLASS | TR205 | TR208 | TR210 | TR214 | TR216 | |
Creepage Distance,mm | 394 | 610 | 940 | 1092 | 1829 | |
Cantilever Strength, kN | 8.9 | 8.9 | 8.9 | 8.9 | 6.7 | |
Tension Strength, kN | 38 | 44.5 | 53 | 62 | 71 | |
Torsion Strength N.m | 791 | 904 | 1130 | 1356 | 1695 | |
Compression Strength, kN | 44.5 | 44.5 | 66.7 | 66.7 | 111 | |
Low Frequency Flashover Voltage, kV | Dry | 85 | 110 | 145 | 170 | 235 |
Wet | 55 | 75 | 100 | 125 | 180 | |
Critical Impulse Flashover Voltage,kV | Positive | 125 | 170 | 225 | 280 | 390 |
Negative | 200 | 250 | 290 | 340 | 475 | |
Low Frequency Withstand Voltage, KV | Dry | 50 | 70 | 95 | 120 | 175 |
Wet | 45 | 60 | 80 | 100 | 145 | |
Impulse Withstand Voltage, kV | 110 | 150 | 200 | 250 | 350 | |
Weight, kg | 7 | 11 | 16 | 21 | 30 |