FORNEY Integrated Flame Detector D85 Series
Nanjing Win Union Automation and Control Technology Co., Ltd.
Sales : Tonny
skype:yluedq qq:994274685
TEL: ( 86-25)-52791167 52791168
FAX: ( 86-25)-52791169
E-mail: njxj888@163.com
Add: Jiangning Shuanglong Avenue No.1222 Nanjing, Jiangsu. China 211100
Forney’s D85 series fl ame detectors
provide unparalleled ease of installation
and operation, with fully automatic
fl ame characterization and optimum
gain detection.
Housing Material: Standard Models: Engineered material - GE Valox CEX Models: Aluminum, painted fi nish
Standard Models: NEMA 4X, IP66 / Class I Div II CEX Models: Ex II 2 G/D, ATEX certifi ed
Detector Weight: Standard Models: 3.30 lbs (1.5kg) CEX Models: 9.5 lbs (4.3kg)
Cooling / Purge Air
Requirements:
Source: Clean, dry, cool
Volume: 10 SCFM (113 l/min) at 3/8” threaded mounting fl ange, or 1 inch “Y” fi tting, mounted on scanner sight pipe. Temperature near
the upper limit of the operating range and/or dirty fuels may require up to 15 SCFM (425 l/min).
Pressure: Adequate to overcome furnace or windbox pressure
Environmental: -40° F to + 150°F (-40°C to +65°C), 0-95% relative humidity, non-condensing
Forney Flame Detector, Forney Flame Detector, Forney Flame Detector, Forney Flame Detector, Forney Flame Detector, Forney Flame Relay, Forney UV Flame Sensor, Forney Processor, Forney Infrared Probe, etc.
The Forney PM-DR-6101E amplifier is a stand-alone intelligent controller consisting of two printed circuit boards (PCBs) with a cover base. One of the PCBs includes a combination of power supplies, relays, and output / input (I / O) interface software. Another PCB includes microprocessors, stabilizers and signal processing electronics. The entire unit can be installed in a separate cabinet. IDD-II infrared filter with filter, IDD-IIU without filter infrared probe, UV-4 probe, DR-6 IDD / UV probe.
D Furnace Flame Detector Uniflame 95 Series
Overview: FORNEY UNIFLAME series flame detectors are based on microprocessor-based flame detectors using solid-state infrared sensors (IR), UV sensors (UV) and dual sensors (IR UV). The detectors are equipped with an internal flame relay and can adjust the ON / OFF threshold, so no remote flame amplifiers are required. The UNIFLAME 95 series detector combines the principles and characteristics of the FORNEY DPD Flame Detector to detect the presence or absence of a target flame in a single burner or multiple burner conditions. The UNIFLAME 95 series detector detects the modulation amplitude of the target flame (ie, the flicker characteristic of the flame). In the setting procedure of the detector, the modulation frequency characteristic which produces the optimum flame ON / OFF