heat shrinkable terminal for XLPE/PILC cable
USD $5 - $200 /Set
Min.Order:50 Sets
Realyou Power International Development Co., Ltd. (Dalian)
Cat No. | VoltageUo/U(Um) | Type | Cable cross section(mm2) | Cable type |
Heat shrinkable outdoor terminations for 6.35/11(12)kV to 12/20(24)kV,3 core plastic insulated cable with tape/wire screen & SWA. | ||||
1 | 6.35/11(12)kV | TK-HSTO-11/3x50-95 | 50-95 | A |
2 | 6.35/11(12)kV | TK-HSTO-11/3x120-150 | 120-150 | A |
3 | 6.35/11(12)kV | TK-HSTO-11/3x185-240 | 185-240 | A |
4 | 6.35/11(12)kV | TK-HSTO-11/3x300-400 | 300-400 | A |
5 | 8.7/15/(17.5)kV | TK-HSTO-15/3x50-95 | 50-95 | A |
6 | 8.7/15/(17.5)kV | TK-HSTO-15/3x120-185 | 120-185 | A |
7 | 8.7/15/(17.5)kV | TK-HSTO-15/3x240-300 | 240-300 | A |
8 | 12/20(24)kV | TK-HSTO-20/3x50-95 | 50-95 | A |
9 | 12/20(24)kV | TK-HSTO-20/3x120-185 | 120-185 | A |
10 | 12/20(24)kV | TK-HSTO-20/3x240-300 | 240-300 | A |
Heat shrinkable outdoor terminations for 6.35/11(12)kV to 12/20(24)kV,single-core plastic insulated cable with tape/wire screen. | ||||
1 | 6.35/11(12)kV | TK-HSTO-11/1x50-95 | 50-95 | UA |
2 | 6.35/11(12)kV | TK-HSTO-11/1x120-150 | 120-150 | UA |
3 | 6.35/11(12)kV | TK-HSTO-11/1x185-240 | 185-240 | UA |
4 | 6.35/11(12)kV | TK-HSTO-11/1x300-400 | 300-400 | UA |
5 | 8.7/15/(17.5)kV | TK-HSTO-15/1x50-95 | 50-95 | UA |
6 | 8.7/15/(17.5)kV | HKSJ-15/1x120-185 | 120-185 | UA |
7 | 8.7/15/(17.5)kV | TK-HSTO-15/1x240-300 | 240-300 | UA |
8 | 12/20(24)kV | TK-HSTO-20/1x50-95 | 50-95 | UA |
9 | 12/20(24)kV | TK-HSTO-20/1x120-185 | 120-185 | UA |
10 | 12/20(24)kV | TK-HSTO-20/1x240-300 | 240-300 | UA |
Test sequence | Item | Requirements acc. to IEC 60502.4 | Remarks | |
8.7/15(17.5)kV | 12/20(24)kV | IEC 60502.4 | ||
1 | AC withstand voltage test (in air and ambient temperature) | AC for 5 min. at 39kV. No breakdown, No flashover | AC for 5 min. at 54kV. No breakdown, No flashover | PASS |
2 | Partial discharge | 10pC max. at 15kV | 10pC max. at 20kV | PASS |
3 | Impulse withstand test | 10 impulses of each polarity at 95kV | 10 impulses of each polarity at 125kV | PASS |
4 | Heating cycles in air | 30 cycles at 95°C--100°C and 22kV in air, No breakdown, No flashover | 30 cycles at 95°C--100°C and 30kV in air, No breakdown, No flashover | PASS |
5 | Heating cycles under water | 30 cycles at 95°C--100°C and 22kV under water, No breakdown, No flashover | 30 cycles at 95°C--100°C and 30kV under water, No breakdown, No flashover | PASS |
6 | Partial discharge at 95°C--100°C | 10pC max. at 15kV | 10pC max. at 20kV | PASS |
7 | Thermal short-circuit (screen) | No visible deterioration at 3.0 kA, 1s | No visible deterioration at 3.0 kA, 1s | PASS |
8 | Thermal short-circuit (conductor) | No visible deterioration at 23.0 kA, 2s | No visible deterioration at 23.0 kA, 2s | PASS |
9 | Dynamic short-circuit | No visible deterioration at 81.0 kA, not less than 10 ms | No visible deterioration at 81.0 kA, not less than 10 ms | PASS |
10 | Impulse withstand test at 95°C--100°C | 10 impulses of each polarity at 95kV | 10 impulses of each polarity at 125kV | PASS |
11 | AC withstand voltage test | AC for 15 min. at 22kV. No breakdown, No flashover | AC for 15 min. at 30kV. No breakdown, No flashover | PASS |