fire sprinkler,glass bulb fire sprinkler heads,fire sprinkler nozzle zstx-15
USD $0.4 - $1.14 /Piece
Min.Order:2000 Pieces
Quanzhou Sanxing Fire-Fighting Equipment Co., Ltd.
(1). Type: Upright Sprinkler, Pendent Sprinkler, Sidewall Sprinkler, Concealed Sprinkler
(2). Nominal Diameter: 15mm, 20mm
(3). Thread Size: 1/2 inch, 3/4 inch
(4). K Factor: 80, 115
(5). Glass Bulb: 5mm, 3mm
(6). Material: Brass, Zinc
(7). Finish: chrome plated
(8.) Temperature: 57℃, 68°C, 79°C, 93°C, 141°C
(9). Glass Bulb Color: Orange, Red, Yellow, Green, Blue
1.Sprinkler Introduction:
Sprinkler is an important part of wet-type auto spraying system. It is usually installed inside the building and structures with light fire danger, medium fire danger and heavy fire danger, such as workshop, warehouse, hotel, shop, recreational place, hospital, cinema, office building and garage.
The sprinkler is composed of sprinkler frame, sealant and glass bulb. It is to be installed in the protective district via ductwork, acting as a fire detector and auto sprayer. In case of fire inside the protective district, the atmosphere temperature rises up and the liquid inside the glass bulb expands after being heated and explodes after reaching the operating temperature of the glass ball. The sealant drops and the sprinkler sprays to the protective district for fire extinguishments subject to the preset shape of spraying.
2.Installation,Usage and Maintenance:
During installation, should pay attention not to damage the bulb to avoid affect the thermal performance. In the
process of wrench and twist, do not use spanner to wrench the supporting arm to deformation and affect the
sealing performance (note: the bulb temperature can be chosen according to the needs of users)
Pendent Sprinklers: Uesd Mainly, Where water pipeline, used for sprinklers in - stallation is concealed. The sprinkler is mounted in a I discharging spray hemispherically.
Conventional Sprinkles: Used either in Upright or in Pendent Positions producing a spherical pattern with part of water sprayed towards the cell.
Upright Sprinkles: Used mainly where the water pipeline is exposed. Mounded only in Upright position discharging spray hemispherically.
Sidewall Sprinkles: Used mainly, where the pipeline run along the wall, sprinkles form out ward half parboiled pattern.
3.Product Feature:
It can not only detect the fire, but also extinguish the fire by spraying water.
4.Application:
It is usually installed in areas with fire danger, including warehouses, shopping malls, hotels, hospitals, theaters, office building, high-rise building, garages and etc.
5.Avaliable temperature:
Temp. Classification | Ordinary | Ordinary | Intermediate | Intermediate |
Nominal Temp. Rating | 135°F/57°C | 155°F/68°C | 175°F/79°C | 200°F/93°C |
Max. Ambient Temp. Allowed | 115°F/46°C | 135°F/57°C | 155°F/68°C | 180°F/82°C |
Max. Recommended Ambient Temp. | 100°F/38°C | 100°F/38°C | 150°F/65°C | 150°F/65°C |
Glass Bulb Color | Orange | Red | Yellow | Green |
Type | Upright | Pendent | Sidewall | Common | Concealed | ESFR | |||||
Model | ZSTZ | ZSTX | ZSTBS | ZSTP | ZSTDY | ZSTY | |||||
Nominal Diameter (mm) | DN15 | DN20 | DN15 | DN20 | DN15 | DN20 | DN15 | DN20 | DN15 | DN20 | DN20 |
Connecting Threaded (Inch) | 1/2 | 3/4 | 1/2 | 3/4 | 1/2 | 3/4 | 1/2 | 3/4 | 1/2 | 3/4 | 3/4 |
Flux Coefficient | 80 | 115 | 80 | 115 | 80 | 115 | 80 | 115 | 80 | 115 | 115 |
Bulb Diameter | 5mm glass bulb for standard response 3mm glass bulb for quick response | ||||||||||
Response Time | 15seconds in general for 5mm glass bulb 8seconds in general for 3mm glass bulb | ||||||||||
Response Time Index RTI (m·s)0.5 | 87 for 5mm glass bulb
22—25 for 3mm glass bulb |
fire sprinkler Package:200pcs packing in a carton box or according to your requirement
Packing detail
50pcs in 1 inner box , 4 inner boxes=200pcs in 1 carton