14 pins general purpose magnetic plug in Power relay MY4N RXM2CB2BD
USD $1.5 - $2 /Piece
Min.Order:1 Piece
Yueqing Nobel Electric Co., Ltd.
CHRE Zelio Relay RXM.AB Miniature Plug-in Relay
The main purpose of the RXM.AB Miniature Plug-in Relay is to control a circuit by a low-power signal with complete electrical isolation between control and controlled circuits, or where several circuits must be controlled by one signal
This range consists of RXM2AB, RXM3AB, RXM4AB/GB series. The range consists of miniature electromagnetic relays with 2, 3 or 4 C/O contacts with/without LED indicator and push button. The control voltage ranging from 24 Vac to 230 Vac and 12 Vdc.to 220Vdc with rated current 12A. The representative product used for the analysis is RXM2AB2P7. The relay has 2 C/O contacts with LED indicator and push button. The control voltage is 230 Vac 50/60Hz.
The environmental impacts of this referenced product are representative of the impacts of the other products of the range which are developed with a similar technology. The environmental analysis was performed in conformity with ISO 14040
Range of product | Zelio Relay |
Series name | Miniature |
Product or component type | Plug-in relay |
Device short name | RXM |
Utilisation coefficient | 20 % |
Sale per indivisible quantity | 10 |
Contacts operation | Standard |
Control circuit voltage | 230 V AC |
[Ithe] conventional enclosed thermal current | 10 A at -40...55 °C |
Status LED | With |
[Ui] rated insulation voltage | 300 V conforming to UL 250 V conforming to IEC |
[Uimp] rated impulse withstand voltage | 3.6 kV (1.2/50 µs) conforming to IEC 61810-7 |
Contacts material | Silver alloy (Ag/Ni) |
[Ie] rated operational current | 5 A (AC-1/DC-1) NC conforming to IEC 10 A (AC-1/DC-1) NO conforming to IEC 10 A (AC-1/DC-1) conforming to UL |
Minimum switching current | 10 mA |
Maximum switching voltage | 125 V DC 250 V AC |
Minimum switching voltage | 17 V |
Load current | 10 A at 30 V DC 10 A at 250 V AC |
Maximum switching capacity | 300 W network: DC 2500 VA network: AC |
Minimum switching capacity | 170 mW |
Operating rate | <= 18000 cycles/hour no-load <= 1200 cycles/hour under load |
Mechanical durability | 10000000 cycles |
Electrical durability | 100000 cycles for resistive load |
Average consumption in VA | 1.9 AC |
Drop-out voltage threshold | AC: >= 0.15 Uc |
Operating time | 20 ms |
Average resistance | 15000 Ohm network: AC at 20 °C +/- 15 % |
Rated operational voltage limits | 184...253 V AC |
Protection category | RT I |
Operating position | Any position |
CAD overall width | 21 mm |
CAD overall height | 27 mm |
CAD overall depth | 55 mm |
Product weight | 0.035 kg |
Dielectric strength | 1000 V AC between contacts 1550 V AC between poles 1800 V AC between coil and contact |
Product certifications | GOST UL |
Standards | EN/IEC 61810-1 UL 508 |
Ambient air temperature for storage | -40...70 °C |
Ambient air temperature for operation | -40...55 °C |
Vibration resistance | 5 gn, amplitude = +/- 1 mm (f= 10...55 Hz) with clip conforming to EN/IEC 60068-2-6 3 gn, amplitude = +/- 1 mm (f= 10...55 Hz) without clip conforming to EN/IEC 60068-2-6 |
IP degree of protection | IP40 conforming to EN/IEC 60529 |
Shock resistance | 10 gn (duration = 11 ms) for closing conforming to EN/IEC 60068-2-27 10 gn (duration = 11 ms) for opening conforming to EN/IEC 60068-2-27 |