24V 20A single switching power supply(SP-500-24)

Place of Origin Zhejiang, China
Brand Name LIRRD
Model Number SP-500-24
Output Power 401 - 500W
Output Type Single
Input Voltage 220V
Output Voltage 24V
Output Current 20A

Product Features

Specifications

24V 20A single switching power supply(SP-500-24)
CE certificate, better rediating effect
competitve price, high quality

24V 20A single switching power supply(SP-500-24)

  • 500W ac/dc switch power supply
  • Competitived price and high reliability
  • 105oC Output capacitor
  • AC input power suitable for the world
  • High efficiency and low operation temperature
  • Soft-start current can reduce the AC input impact effeciticly
  • With short-circuit and overload protection
  • Compact size, light weight
  • 100% full-load burn-in test
  • Installed with EMI filter, minimum wave

ModelS-500-12S-500-13.5S-500-15S-500-24S-500-27S-500-48
DC output voltage12V13.5V15V24V27V48V
Output voltage range(Note:2)±1%±1%±1%±1%±1%±1%
Rated output current40A36A32A20A18A10A
Output current range0-40A0-36A0-32A0-20A0-18A0-10A
Wave and noise(Note:3)240mVp-p240mVp-p240mVp-p240mVp-p200mVp-p300mVp-p
Inlet stability(Note:4)±0.5%±0.5%±0.5%±0.5%±0.5%±0.5%
Load stability(Note:5)±1%±0.5%±0.5%±0.5%±0.5%±0.5%
DC output power480W486W480W480W486W480W
Efficiency84%84%83%86%87%87%
Adjustable range for DC voltage10~13.2V12~15V13.5~18V20~26.4V24~30V41~56V
Input current7A/115V 3.5A/230V
AC inrush current18A/115V 36A/230V
Leakage current<0.35mA/240VAC
Overload protection105%~150% Type: pulsing hiccup shutdown Reset: auto recovery
High-temperature protectionERH3 > =55°c Fan on, < =45°c Fan off, > =70 °c,Cut off output(5~15V)
Temperature coefficient±0.03%/°c(0~50°c)
Setup, rise , hold up time1.5s,50ms, 20ms
Vibration10~500Hz, 2G 10min,/1cycle, Period for 60min, Each axes
Withstand voltageInput and output internal: 1.5KvAC, Input and enclosure:1.5KvAC, Output and enclosure:0.5KvAC
Working temperature and humidity -10°c~+60°c(Refer to output derating curve), 20%~90%RH
Weight1.8Kgs
Safety standardsMeet UL 1950 requirement (Not apply for the mark)
EMC standardsCISPR22(EN55022), IEC1000-4,2,3,4,5,6,8,99 IEC1000-3-2

Note:                                                                                                                                                                1. The testing condition for the paramenter above is: 230VAC input, rated load, 25°c 70% RH. Temperatuer.                

.2. Error: include the setting error, line stability and load stability.(Note:5)                                                               

3. Wave test: adopting "A12" double wire for 20MHz, and 0.1UF&47UF capacitor short-circuit for interrupting.           

4. Inlet woltage stability test: when is over load, the lowest voltage of inlet is up to the highest voltage.                     

5. Load stability test: The load is from 0% to 100%                                                                     