Product Details

ZLA Transformer Oil Purification System

Condition New
Flow depends on actual model
Working Pressure 0.05~0.3Mpa
Place of Origin Chongqing, China
Brand Name junneng transformer oil purification
Model Number ZLA transformer oil purification
Usage Other, transformer oil purification
Voltage 380V(or depends on actual product)
Power(W) 50HZ
Dimension(L*W*H) depends on model
Weight depends on model
Certification ISO9001
After-sales Service Provided Engineers available to service machinery overseas

Product Features

ZLA transformer oil purification system

 

 

 

overview:

ZLA series double stage vacuum oil purifier is manufactured according to standards, which go beyond Chinese legal criterion, dealing with almost insulation oil of power equipment more rapidly and effectively with the supporting of high vacuum and speed absorption. Thus the strength of insulation oil is much increased and shortens the dealing time.

ZLA Transformer Oil Purification System

 

Features:

1) Manufactured as per standards which go beyond the legal criterion. A primary breakdown voltage can raise 35KV and reduces the oil damage causing by normal purifiers due to repeated heating.

2) Large absorption speed double vacuum meets the needs of vacuum zing of transformer on an installation or repair site, at the same time remove the water, gas, and also keep the completeness of transformer oil. It significantly shortens the oil treatment time.

3) The unique gas, water removal system adopting stereo-evaporation technology, which rapidly separates the water and gas in the oil and is free of maintenance.

4) A superior purification system with top quality filter core, which can accommodate large quantity of impurities and is progressively dandified step by step. It has been got a high precision and multi-stage filtration.

5) Imported parts adopt all electric system, which ensures high performance.

6) Advanced infrared liquid level control system with automatic control, allowing separated operation of manual operators from a machine.

7) Interlocked safety protection device. i.e., backflow of A oil outlet over pressure can be achieved via an overflow valve, B oil inlet will interlock with heating system which avoids any possible negative impacts caused by mal-operation

8) Precision oil pumps have low noise and environmental regulatory compliance will be well met.

 

Technical Parameters:

 

Model

Unit

ZLA-30

ZLA-50

ZLA-70

ZLA-100

ZLA-150

ZLA-200

ZLA-300

Rated flow

L/min

30

50

70

100

150

200

300

Vacuum Range

Mpa

-0.05~-0.099

Temperature Range

°C

40~80

Oil pump pressure

Mpa

0.05~0.3

Total Power

kw

38

46

62

90

120

144

195

Power

 

50HZ   380V

Working Noise

db(A)

≤65~85

Cleanliness

NAS1638

≤NAS 6

Breakdown Voltage

kv

≥75

Water content in oil

PPM

≤5

Gas content in oil

%

≤0.05

Filter precision

µm

≤3

Inlet (outlet) diameter

 

25

32

32

42

50

60

65

Dimension(mm)

 

L

1480

1600

1650

1700

1800

2000

2100

W

980

1100

1200

1200

1300

1500

1600

H

1300

1400

1600

1800

1800

1900

1900

 

Dimension and weight will be changed with changing the technical specification.