PVC Insulated Wire With Rated Voltage Up To 450/750
Negotiable /Kilometer
Min.Order:1 Kilometer
Application:
The PVC Insulated Wire belong to the series of laying wires, which are mainly suitable for laying at the fixed place.
They are widely used as connectors of driving, lighting, electric equipment, instrument and telecommunication
equipment with rated voltage up to 450/750V. Part of the plastic insulated wires are used at the equipment with AC
rated voltage up to 300/300V.
Comprehensive Data of BV Wire
Nominal Sectional Area | Conductor No./Dia. | Nominal Insulated Thickness | Max.Overall Dia. | Max.D.C.Conductor Resistance at 20°c | Min. Insulated Resistance at 70°c | Weight |
mm² | mm | mm | mm | Ω/km | mΩ/km | kg/km |
0.5 | 1/0.80 | 0.6 | 2.4 | 36.0 | 0.015 | 8.1 |
0.75 | 1/0.97 | 0.6 | 2.6 | 24.5 | 0.012 | 10.6 |
1 | 1/1.13 | 0.6 | 2.8 | 18.1 | 0.011 | 13.2 |
Standards
Nominal Sectional Area | Conductor No./Dia. | Nominal Insulated Thickness | Max.Overall Dia. | Max.D.C.Conductor Resistance at 20° Cu Al | Min. Insulated Resistance at 70°c |
Weight Cu Al |
mm² | mm | mm | mm | Ω/km | mΩ/km | kg/km |
1.5 | 1/1.38 | 0.7 | 3.3 | 12.1 / | 0.011 | 19.2 / |
1.5 | 7/0.52 | 0.7 | 3.5 | 12.1 / | 0.010 | 20.6 / |
2.5 | 1/1.78 | 0.8 | 3.9 | 7.41 11.8 | 0.010 | 30.8 15.0 |
4 | 1/2.25 | 0.8 | 4.4 | 4.61 7.39 | 0.0085 | 45.5 21.0 |
6 | 1/2.76 | 0.8 | 4.9 | 3.08 4.91 | 0.0070 | 65.0 29.0 |
10 | 7/1.35 | 1.0 | 7.0 | 1.83 3.08 | 0.0065 | 110.0 52.0 |
16 | 7/1.70 | 1.0 | 8..0 | 1.15 1.91 | 0.0060 | 170.0 70.0 |
25 | 7/2.14 | 1.2 | 10.0 | 0.727 1.20 | 0.0060 | 270.0 110.0 |
35 | 7/2.52 | 1.2 | 11.5 | 0.524 0.868 | 0.0040 | 364.0 150.0 |
50 | 19/1.78 | 1.4 | 13.0 | 0.387 0.641 | 0.0045 | 500.0 200.0 |
70 | 19/2.14 | 1.4 | 15.0 | 0.268 0.443 | 0.0035 | 688.0 269.0 |
95 | 19/2.52 | 1.6 | 17.5 | 0.193 0.320 | 0.0035 | 953.0 360.0 |
120 | 37/2.03 | 1.6 | 19.0 | 0.153 0.253 | 0.0032 | 1168.0 449.0 |
150 | 37/2.25 | 1.8 | 21.0 | 0.124 0.206 | 0.0032 | 1466.0 551.0 |
185 | 37/2.52 | 2.0 | 32.5 | 0.099 0.164 | 0.0032 | 1808.0 668.0 |