motor soft start up cabinet with breaker 3phase 380V 30KW soft starter for Heat pump
USD $150 - $5,000 /Piece
Min.Order:1 Piece
Shenzhen EMHEATER Technology Limited
EM-GJ series Soft Starter cabinet
Brief Imformation:
EM-GJ series Soft Starter is a new type start-up equipment which integrates electric force and electronic techniques, computer technique and modern control theory. It is the new generation product to replace the conventional Star-delta Starter, Self-coupling voltage-drop Starter and Magnetic control voltage-drop Starter.
Feature:
Item | Description | |
Input Power Supply | Input Voltage | Three-phase 220V/380V/480V AC |
Frequency | 50/60Hz | |
Adaptive Motor | Squirrel-cage three-phase asynchronous motor | |
Starting Times | It is recommended not to exceed 20 times per hour. | |
Control Mode | (1) Operation panel control; (2) Operation panel + external control; (3) External control; (4) External control + COM control; (5) Operation panel + external + COM control; (6) Operation panel + COM control; (7) COM control; (8) No start or stop operation. | |
Start Mode | (1) Current-limiting start; (2) Voltage ramp start; (3) Kick start + current-limiting start; (4) Kick start + voltage ramp start; (5) Current ramp start; (6) Voltage current-limiting double closed-loop start. | |
Stop Mode | (1) Soft stop; (2) Free stop. | |
Protective Function | (1)Open loop protection for external instantaneous stop terminals; (2) Over-heat protection for soft starter; (3) Protection for too long starting time; (4) Input open phase protection; (5) Output open phase protection; (6) Unbalanced three-phase protection; (7) starting over current protection; (8) Running overload protection; (9) Under voltage protection for power voltage; (10) Overvoltage protection for power voltage; (11) Protection for fault parameter setting; (12) Load short circuit protection; (13) Auto restart or incorrect wiring protection; (14)Incorrect wiring protection of external control stop terminals. | |
Ambient | Place to be used | Indoor location with good ventilation free from corrosive gas and conductive dust. |
Altitude | Below 3000M. It have to rise the rate power when the altitude is more than 3000M. | |
Temperature | -30 +55 oC | |
Humidity | 90%RH without dew condensation. | |
Vibration | <0.5G | |
Structure | Protection Class | IP20 |
Cooling Pattern | Natural wind cooling. |
Soft starter connection and main circuit connetion diagram:
Soft starter connection diagram
Main circuit connection diagram
Factory to shoot:
Application:
The loading | Voltage ramp starting time(s) | Voltage ramp stopping time(s) | Initial voltage | Voltage ramp (current limit) | Current limit to start |
Ball mill machine | 20 | 6 | 60% | 400% | 350% |
Fan | 26 | 4 | 30% | 400% | 350% |
Centrifugal | 16 | 20 | 40% | 400% | 250% |
Piston compressor | 16 | 4 | 40% | 400% | 300% |
Lift | 16 | 10 | 60% | 400% | 350% |
Stirring machine | 16 | 2 | 50% | 400% | 300% |
Breaker | 16 | 10 | 50% | 400% | 350% |
Screw compressor | 16 | 2 | 40% | 400% | 300% |
Rotating conveyor | 20 | 10 | 40% | 400% | 200% |
Light load | 16 | 2 | 30% | 400% | 300% |
Convey belt | 20 | 10 | 40% | 400% | 250% |
Heat pump | 16 | 20 | 40% | 400% | 300% |