EM415-Mod MID approved single phase electric modbus energy meter
Negotiable /Unit
Min.Order:100 Units
Shanghai Fangqiu Electric Co., Ltd.
EM737 CT MID approved digital energy consumption meter german lcd display electric meter
EM418 MID approved 1 phase 220v din rail power meter 10(100)A watt meter class B energy meter
EM735 ct connected meter 3 phase 4 wire energy meter connection 230v s0 output din rail power meter
PM837 three phase digital ac power meter multi rates digital panel meter 96*96mm
EM415-Mod MID approved single phase electric modbus energy meter
Main Functions and features:
MID approved single phase metering power meter
Standard DIN rail Format (DIN43880)
IEC62053-21/22 Class 1.0,0.5S
LCD display, 6 integer 2 decimal
Large clear backlight display
Direct metering up to 100A
Smart communication port, RS485 Modbus RTU
Program by button on the nameplate
Memory back-up (EEprom)
4 DIN modules
Performance criteria
Operating humidity ≤ 75%
Storage humidity ≤ 95%
Operating temperature -5°C - +45°C(3K5)
Storage temperature -25°C - +55°C(3K6)
Humanity 75% yearly average,95% on 30 days/year
International standard EN50470-3 &IEC62053-21
Accuracy class CI.1
Protection against penetration of dust and water IP51
Insulating encased meter protective class Ⅱ
Connection area main terminals
Current terminals flexible 1×mm2 0-16mm2
another terminal flexible 1×mm2 0-2.5mm2
Meter specification
| Direct connected meters |
Voltage(v) | 230V |
Operational voltage | ±70%Un |
- Iref | 10A |
-Itr | 1A |
-Imax | 100A |
-Imin | 0.5A |
-Ist | 40mA |
Power consumption of current circuits(VA) | < 0.01 |
Power consumption of voltage circuits(W) | < 1.3W |
General data |
|
Frequency (Hz) | 50/60 |
Memory back-up | EEprom |
Environment resistance to heat and fire | Terminal 960°C Cover 650°C |
Time-keeping accuracy | <0.5s/day |
Clock operating with battery | >15 years |
Power off clock running time | >5 years |
upper | ABS+PC |
lower | ABS+PC |
Pulse output |
|
Pulse width(ms) | 80 |
Pulse constant(imp/kWh) | 400 |
LED constant | 400 |
Width (mm) | 126 |
Height (mm) | 104.5 |
Depth (mm) | 60 |
Pulse output function
Smart meter is equipped with a pulse output which is fully separated from the inside circuit. That generates pulses in proportion to the measured energy .include the testing pulse output of active energy and reactive energy. 14/ 15 Test pulse output contact (P+/P-),13/ 15 Test pulse output contact (Q+/Q-)
The test pulse output is a polarity dependant, passive transistor output requiring an external voltage source for correct operation.
Reading the meter
The smart energy meter is equipped with 6+2 LCD display, which is used as recording consumption and can’t be reset to zero. The number system is based on units of 10. And unit is kWh.
Communication port
Smart meter has equipped communication port, we can program the meter’s operation data or reading via these 2 ports.(Pin26 pin27) .
Programming
The meter can be programmed by pressing button on the panel such as Modbus ID, password,Baudrate etc..
Other products: