EM427 CT 120/240V 1.5(6)A ct operated two phase smart bi-directional modbus electric energy meter
USD $10 - $60 /Unit
Min.Order:200 Units
Shanghai Fangqiu Electric Co., Ltd.
EM427 CT two phase smart bi-directional modbus electric energy meter
EM12100RS type single-phase three-wire Electronic Socket Meter Round Meter electronic meter
EM415-Mod MID approved single phase din rail kwh meter rs485 digital energy meter
EM415-Mod MID approved single phase electric modbus energy meter
EM427 CT 120/240V 1.5(6)A ct operated
two phase smart bi-directional modbus electric energy meter
specification :
Electrical Characteristics | EM427 CT |
Voltage(v) | 120/240V |
Operational voltage | (70-130)%Un |
Current(A) | |
- Iref | 1.5A |
-Itr | 0.15A |
-Imax | 6A |
-Imin | 0.075A |
-Ist | 3mA |
Power consumption of current circuits(VA) | < 0.01 |
Power consumption of voltage circuits(W) | < 1.3W |
General data | |
Frequency (Hz) | 50/60 |
Memory back-up | EEprom |
Environment resistance to heat and fire | Terminal 960°C Cover 650°C |
Enclosure material | |
upper | ABS+PC |
lower | ABS+PC |
Pulse output | |
Pulse width(ms) | 80 |
Pulse constant(imp/kWh) | 6400 |
LED | |
LED constant | 6400 |
Dimension | |
Width (mm) | 72 |
Height (mm) | 104.5 |
Depth (mm) | 60 |
Dimension :
Wiring diagrams:
3 Wire with RS485:
2 wire with RS485 :
Main function:
Measuring Function:
Meter can measure import & export active energy , import & export reactive energy.
Display function :
Smart meter have two status: cycle display status andbutton press display .When pressing the button, User can set according their request. Button press will Backlight the LCD. Display cycle can be set within 5~20 seconds, The default is 5 seconds.
Electricity parameters measurement and monitoring :
Measure record and display voltage, current, power and power factors. error is not more than ±1%.
Communication Function :
With an infrared COM and a RS485 COM. Communication protocols fit Modbus RTU standard. RS485 communications transfer rates allow selected at 1200bps, 2400bps, 4800 bps and 9600bps, default is 9600bps.
Alarm function:
When the meter connect wire wrong example: current reverse, the meter will display , the ALARM led will be on.
Pulse output function :
Smart meter is equipped with a pulse output which is fully separated from the inside circuit. That generates pulses in proportion to the measured energy .include the testing pulse output of active energy and reactive energy. 8/ 11 Test pulse output contact (P+/P-).
CT ratio setting function :
Press “Pagedown” and “pageup” buttons to select the CT transformation ratio press “SET” button to save the setup .
Other products: