Power Harmonics and Leakage Tester
Negotiable /Piece
Min.Order:1 Piece
Shanghai Sunlight Electronic Technology Company Limited
Feature:
MODEL PROVA 19, 21, 23
True RMS value (V and A)
Leakage Current Measurement at 10 μ A Resolution
Harmonic Analysis (V and A) to the 99 th Order
Better Understanding of High Frequency Harmonic Analysis (up to 5/6 KHz)
Non-interrupted Harmonic Analysis
Analysis of Total Harmonic Distortion (THD-F)
Analysis of Crest Factor (C.F.)
Fast Peak Function (33 μ s and 39 μ s)
Programmable CT Ratio (1 to 250)
Model 21(50A) and 23(100A)
W, KW, H.P.
VA, KVA, VAR, KVAR
PF, Phase Angle ( Φ )
Energy (mWH, WH, KWH)
Analysis of Standby Power Consumption
Balanced 3 Φ Power Quality
Specifications:
AC Watt (50 or 60 Hz, PF 0.5 to 1. CT = 1, Accuracy of Readings)
Model 21 (0 to 50A), Model 23 (0 to 100A)
Range | Resolution | Accuracy 21 (0 - 30A) Accuracy 23 (0 - 60A) | Accuracy 21 (30 - 50A) Accuracy 23 (60 - 100A) |
0.000 - 9.999 W | 0.001 W | +/-1% +/- 0.02 W | +/-2% of VA +/- 5dgts |
10.00 - 99.99 W | 0.01 W | +/-1% +/- 0.2 W | +/-2% of VA +/- 5dgts |
100.0 - 999.9 W | 0.1 W | +/-1% +/- 0.2 W | +/-2% of VA +/- 5dgts |
1.000 - 9.999 KW | 0.001 KW | +/-1% +/- 0.02 KW | +/-2% of VA +/- 5dgts |
10.00 - 99.99 KW | 0.01 KW | +/-1% +/- 0.2 KW | +/-2% of VA +/- 5dgts |
100.0 - 999.9 KW | 0.1 KW | +/-1% +/- 0.2 KW | +/-2% of VA +/- 5dgts |
1000 - 9999 KW | 1 KW | +/-1% +/- 2 KW | +/-2% of VA +/- 5dgts |
AC Current (50 or 60 Hz, True RMS)
Range (Model 19,21) | Range (Model 23) | Resolution | Accuracy of Readings |
0.30 - 60.00mA | 0.30 - 60.00mA | 0.01mA | +/-0.5% +/- 5dgts |
60.0 - 600.0mA | 60.0 - 600.0mA | 0.1mA | +/-0.5% +/- 5dgts |
0.030 - 3.000 A | 0.030 - 9.999 A | 0.001 A | +/-0.5% +/- 5dgts |
3.00 - 30.00 A | 10.00 - 60.00 A | 0.01 A | +/-0.5% +/- 5dgts |
30.00 - 50.00 A | 6 0.00 - 99.99 A | 0.01 A | +/-1.0% +/- 5dgts |
AC Voltage (50 or 60 Hz, True RMS)
Range | Resolution | Accuracy of R. | Range | Resolution | Accuracy of R. |
3V - 250V | 0.1 V | +/-0.5% +/- 5dgts | 250V - 600V | 0.1 V | +/-0.5% +/- 5dgts |
Harmonics of AC Voltage in % and Magnitude (1 to 99th order)
Range | Resolution | Accuracy in % | Resolution | Accuracy in Magnitude |
50V - 600V | 0.1 % | +/-0.5% | 0.1 V | +/-0.5% +/- 0.5V |
Harmonics of ACA in % Percentage and Magnitude (1 to 99th order)
Range (Model 19, 21) | Range (Model 23) | Res. | Accuracy (%) | Res. | Accuracy of R. |
10.00 - 60.00mA | 10.00 - 60.00mA | 0.1 % | +/-0.5% | 0.01mA | +/-0.5% +/- 0.1mA |
60.0 - 600.0mA | 60.0 - 600.0mA | 0.1 % | +/-0.5% | 0.1mA | +/-0.5% +/- 1mA |
0.5 - 3.000 A | 0.5 - 9.999 A | 0.1 % | +/-0.5% | 0.001 A | +/-0.5% +/- 0.01 A |
3.00 - 30.00 A | 10.00 - 60.00 A | 0.1 % | +/-0.5% | 0.01 A | +/-0.5% +/- 0.1 A |
30.00 - 60.00 A | 6 0.00 - 99.99 A | 0.1 % | +/-1.0% | 0.01 A | +/-1.0% +/- 0.1 A |
Power Factor and Phase Angle (PF, Φ ,Model 21 and 23)
Range (PF) | Resolution | Accuracy | Range (Φ) | Resolution | Accuracy |
0.000 - 1.000 | 0.001 | +/- 1° | -180° to 180° (0 ° to 360 ° ) | 0.1° | +/- 1° |
Total Harmonic Distortion (THD-F, 1 to 99th order) Crest Factor (C.F., Accuracy of Readings)
Range | Resolution | Accuracy of R. | Range | Resolution | Accuracy of R. |
0.0 - 999.9 % | 0.1% | +/- 0.5% +/- 5 digits | 1.00 - 99.99 | 0.01 | +/- 5% +/- 30 digits |
General Specification
Conductor Size | 30mm (appro*.) |
Battery Type | 1.5V SUM-3 * 2 |
Display | 4+2+2 digits LCD |
Power Consumption | 5mA (appro*.) |
Auto-Power-Off | 30 minutes |
No. Of Samples/Period | 512 (V & A), 256 (W) |
LCD update rate | 2 times / sec. |
Weight | 200g (battery included) |
Operating Temperature | -10 ° C to 50° C |
Operating Humidity | < 85% relative |
Storage Temperature | -20° C to 60° C |
Storage Humidity | < 75% relative |
Dimension | 210 (L) * 62 (W) * 35.6mm (H), 8.3" (L) * 2.5" (W) * 1.4" (H) |
Accessories | test leads, Carrying bag * 1, Users manual * 1, Batteries 1.5V * 2 |
Option | alligator clips |