UNI-T UT595 Multifunction Loop Testers Earth Ground Line Loop Impedance Tester Insulation Resistance Meter w/RCD Protection
USD $1 - $110 /Piece
Min.Order:1 Piece
Shenzhen Graigar Technology Co., Ltd.
UNI-T UT595 Multifunction Loop Testers Earth Ground Line Loop Impedance Tester Insulation Resistance Meter w/RCD Protection
Introduction
UT595 is a kind of comprehensive digital multifunctional electrical safety test instrument. The overall instrument adopts new design as well as large-scale integrated analogy circuits, digital circuits and microcomputer chip combination. It is mainly used to complete measurement of parameters including (RCD) electric leakage protector, loop circuit/line impedance, grounding continuity test, test insulation resistance, DC voltage, AC voltage and phase sequence judgment; it has more functions, higher accuracy and stable performance as well as it is reliable and convenient for operation. It is applicable to measuring (RCD) electric leakage protector, measuring insulation of various electrical equipment and grounding continuity test. UT595 is your ideal choice for maintenance, test and inspection on electric protector of various electrical equipment.
Contrasrt
Specifications | Range | Best Accuracy | |
Model | UT595 | ||
Insulation Resistance (Ω) | Test Voltages | 250V/500V/1000V | ±10% |
250V | 0.05MΩ-250MΩ | ±(5%+5) | |
500V | 0.05MΩ-500MΩ | ||
1000V | 0.05MΩ-1000MΩ | ||
Short-Circuit Current | <2mA | √ | |
Low Resistance Continuity Test(Ω) | Range | 0.00Ω-199Ω | ±(2%+5) |
Test Current | 0.002Ω: >200mA | √ | |
Line Impedance (Ω) | Range | 0.01Ω~2000Ω | ±(5%+5) |
Operational Voltage(Freq.) | 195V-440V(45Hz-65Hz) | √ | |
Test Current | 20A | √ | |
PFC Range | 0KA-26KA | √ | |
Loop Impedance (Ω) | Range | 0.01Ω-2000Ω | ±(5%+5) |
Operational Voltage(Freq.) | 195V-253V(45Hz-65Hz) | √ | |
Test Current | 20A | √ | |
PFC Range | 0KA-26KA | √ | |
Loop Impedance Without Tripping(Ω) | Range | 1.00Ω-2000Ω | ±(5%+5) |
Operational Voltage(Freq.) | 195V-253V(45Hz-65Hz) | √ | |
Test Current | 15mA | √ | |
PFC Range | 0KA-26KA | √ | |
RCD | Operational Voltage(Freq.) | 195V-253V(45Hz-65Hz) | √ |
Test Current | 10mA/30mA/100mA/300mA/500mA | ±10% | |
Trip Time | ×1/2 *In Range: 0ms-2000ms | ±(5%+5) | |
×1 *In Range: 0ms-300ms | ±(5%+5) | ||
×1 *In Range: 0ms-500ms(Selective Countdown) | ±(5%+5) | ||
×2 *In Range: 0ms-300ms | ±(5%+5) | ||
×2 *In Range: 0ms-500ms(Selective Countdown) | ±(5%+5) | ||
×5 *In Range: 0ms-40ms | ±(5%+5) | ||
Phase Sequence Test | Operational Voltage(Freq.) | 100V-440V(45Hz-65Hz) | √ |
Indication | Order: L1→ L2→ L3 Positive change L1→ L3→ L2 To reverse | √ | |
RCD Measurement RAMP Slope | Test Current Range | 10mA/30mA/100mA/300mA/500mA | ±10% |
AC Voltage (V) | Range | 0V-440V | ±(5%+2) |
Frequency Response | 45Hz-60Hz | √ | |
Resolution | 1V | √ | |
Features | |||
Display Count | 9999 | ||
Auto Power Off | √ | ||
Low Battery Indication | √ | ||
Data Logging | √ | ||
LCD Backlight | √ | ||
Auto Half-wave Test | √ | ||
RCD Countdown Measurement | 30 Seconds | √ | |
RCD Half-wave Test | √ | ||
Phase Switch(RCD) | 0°and 180° | √ | |
General Characteristic | |||
Power | 1.5V Batteries(LR6) X 6 | ||
LCD Size | 125mm X 37mm | ||
Product Color | Red and Grey | ||
Product Net Weight | 1000g | ||
Product Size | 210mm X 175mm X90 mm | ||
Standard Accessories | Batteries, Test Lead (1 x Green, 1x Black, 1 x Red), Specialized Test Lead, Remote Control Test Lead | ||
Standard Individual Packing | Gift Box, Tool Box, User Manual | ||
Standard Quantity Per Carton | 4 PCs | ||
Standard Carton Measurement | 510mm X 330mm X 300mm (0.051CBM Per Standard Carton) | ||
Standard Carton Gross Weight | 15Kg |
Fitting
Batteries, (not included)
Test Lead (1 x Green, 1x Black, 1 x Red),
Specialized Test Lead,
Remote Control Test Lead
(Julie Zhou)