Electrical data (Ta=25ºC±5ºC,RL=2KΩ,CL=10000PF) |
Type | K104- 1000A | K104- 2000A | K104- 3000A | K104- 4000A | K104- 5000A | Unit |
Rated current(Ipn) | ±1000 | ±2000 | ±3000 | ±4000 | ±5000 | A |
Measure range(Ip) | 0-±2000 | 0-±3000 | 0-±4500 | 0-±6000 | 0-±7500 | A |
Rated output | @Ip=±Ipn ±4±1% | V | ||||
Supply voltage | ±12,±15 | V | ||||
Power Consumption | <25 | mA | ||||
Offset voltage | @Ip=0 ±20 | mV | ||||
Magnetic offset | @Ip=±Ipn-0 ±20 | mV | ||||
Offset drift | @ -40~+85ºC ≤±1 | mV/ºC | ||||
Output drift | @ -40~+85ºC ≤±1 | mV/ºC | ||||
Linearity | @Ip=0-±Ipn ≤1 | %FS | ||||
Response time | @50A/μS, 10%-90% ≤7 | μs | ||||
Galvanic isolation | @ 50HZ,AC,1min 6 | KV |
Applications |
·Variable speed drives
·Welding machine
·Battery supplied applications
·Uninterruptible Power Supplies (UPS)
·Electrochemical
Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm.
3. Elucidation: 1:+15V 2:-15V 3:V0UT 4:0V
Directions for use |
1. When the current will be measured goes through a sensor, the voltage will be measured at the output end.(Note: The false wiring may result in the damage of the sensor)
2.Custom design in the different rated input current and the output voltage are available.
Standards |
·UL94-V0.
·EN60947-1:2004
·IEC60950-1:2001
·EN50178:1998
·SJ 20790-2000
General date |
Value | Unit | |
Operating temperature(TA) | -40 to +85 | ºC |
Storage temperature(TS) | -40 to +125 | ºC |
Mass(approx) (M) | 960 | g |