1-in/1-out Low Frequency Online UPS Power Supply (2kVA~20kVA)
USD $365 - $1,450 /Set
Min.Order:1 Set
Qingdao Powtech Electronics Co., Ltd.
Features:
1. High performance systems
-On-line double conversion topology;
-True sine wave output;
-Microprocessor controller;
-Avr design, expanded input voltage range
-Inverter design using IGBT module
2.Well protecions
-Built=in isolation transformer proviede;
-Clean and steady power;
-Lighting and spike protection;
-Electro magnetic/radio frequency interference (EMI/RFI)filter protecion;
-Outstanding overload capacity (Maintains up to 30 seconds of 150% load)
3.User friendly operation
-LED and LCD display UPS statue and internal messages;
-Smart computer interface (RS232 standard);
-Remote monitoring, control and schedule switch On/Power down capable.
2K~20K (1-in/1-out) | |||||||||||||||||||
Model | 2K | 3K | 6K | 10K | 15K | 20K | |||||||||||||
Capacity (VA/W) | 2K/1.6K | 3K/2.4K | 6K/4.8K | 10K/8K | 15K/12K | 20K/16K | |||||||||||||
Input voltage | 220V±25%, 1-phase/3-wire | ||||||||||||||||||
Noise | ≤52dB (distance: 1m) | ≤55dB(distance: 1m) | |||||||||||||||||
Sizes (W×D×H,mm) | 530×240×592 | 624×343×760 | |||||||||||||||||
Weight (Kg) (w/o battery ) | 35 | 35 | 53 | 91 | 110 | 122 | |||||||||||||
Common parameter | |||||||||||||||||||
Input | Frequency | 50Hz/60Hz±10% | |||||||||||||||||
Power factor | ≥92% | ||||||||||||||||||
Output | Voltage | 220V±0.5% | |||||||||||||||||
Voltage regulation | ±1% (static); ±2% (dynamic) (20ms from 0-100% load change) | ||||||||||||||||||
Frequency regulation | 50Hz/60Hz±0.05%(on battery mode) | ||||||||||||||||||
Frequency tracking rate | <1Hz/s | ||||||||||||||||||
Dynamic response | ±0.4%(100% load change) | ||||||||||||||||||
THD | <3% @ linear load (full load); <5% @ non-linear load (full load) | ||||||||||||||||||
Waveform | True sine wave | ||||||||||||||||||
Efficiency | AC input to AC output | ≥91% | |||||||||||||||||
Transfer time | Mains fails or restores | 0s | |||||||||||||||||
Battery | Voltage | 192V for 2K to 20K | |||||||||||||||||
Charge time | 8 hours to 90% | ||||||||||||||||||
Alarm | Battery discharge | Beeps every four (4) seconds when AC mains fails | |||||||||||||||||
Beep every one (1) second when battery voltage low | |||||||||||||||||||
Continuously beeps when stopping battery discharge | |||||||||||||||||||
Fault | Continuously beeps | ||||||||||||||||||
Protection & Display | Battery | Automatically shutdown when battery low, no fuse switch protection. | |||||||||||||||||
Overload | Automatically jumps to BYPSS when 110~150% overload for 30 seconds and automatically resumes when overload removed. | ||||||||||||||||||
Over temperature | Automatically jump to BYPSS when UPS internal temperature >85ºC, | ||||||||||||||||||
Short circuit | Current limit, automatic shutdown, fuse and no fuse switch protection | ||||||||||||||||||
UPS abnormal | Automatically jumps to BYPASS | ||||||||||||||||||
Noise filter | 10~10KHz at 40 db;100KHz~100MHz at 70db | ||||||||||||||||||
LCD display | Display input voltage/frequency, battery voltage and output power (%) | ||||||||||||||||||
Environment | Temperature | -10~40ºC | |||||||||||||||||
Relative humidity | 10%~90%(no condensation) | ||||||||||||||||||
Altitude | 1500m |