High quality Indoor 1 core XLPE 33/35KV Heat shrinkable termination kit/cable termination kits/Power cable terminations
USD $15 - $75 /Set
Min.Order:1 Set
Qingdao Asun Machinery Co., Ltd.
High quality Indoor 1 core XLPE 33/35KV Heat shrinkable termination kit/cable termination kits/Power cable terminations
Features of cable joint:
Technical Data for cable joint
Item No. | Property | Test condition and Requirement | Results |
1 | AC withstand for 1 min.(dry withstand, for indoor termination) | No breakdown and flashover shall occur at 105kV, 1min | No breakdown and flashover occurred on the combi.sample |
2 | Partial discharge | 39kV, ≤10PC | 39kV, ≤10PC |
3 | Load cycle | Heating for 5h, cooling for 3h. Conductor's temperature is 95°C, 3 cycles | Conductor's temperature is 95°C. Results refer to the following test |
4 | Impulse voltage withstand 1.2/50us±10times | 10 positiVe and 10 negative impulses at 250kV, flashover 1 time is allowed but not including total testing times | No breakdown of the combi.sample occurred at 250kV |
5 | DC voltage withstand negative 15 min. | No breakdown and flashover shall occur at 156kV | No breakdown and flashover occurred on the combi.sample |
6 | AC voltage withstand, 4h | No breakdown and flashover shall occur at 104kV, 4h | No breakdown and flashover occurred on the combi.sample |
7 | Oil-seal up test (Only for Paper insulated cables) | Heating for 24h, cooling for 24h. Conductor's temperature is 65°C, oil pressure: 100MPA | No leaking, no seeping |