Specifications
1)Output voltage 220v2)Rated power 1000va
3)built-in batteries
4)True sine wave
5) high Frequency
1. Features
- True on-line double conversion technology with advanced microprocessor control
- Wide input voltage range with high frequency technology
- Zero transfer time
- Protection against all type of power problems
- Self test while start of the UPS
- Site wiring fault warning
- On-battery power-on function
- Smart RS232 communication interface
- Intelligent slot available
- Sealed acid battery, free-maintenance battery
2. Data Sheet
Output | C6KVA/C6KS | C10KVA/C10KS |
Rated Power | 6000VA/4200W | 10000VA/7000W |
Output Voltage | 208VAC/220VAC/230VAC/240VAC | |
Voltage Waveform | Pure Sine wave | |
Crest Factor | 3:1 | |
Output Frequency (Synchronized- Mains) | 46~54Hz or 56Hz - 64Hz (Line mode) 50/60HZ/ ±0.05Hz( Battery mode) | |
Regulation(Nominal) | ±1% | |
Regulation(Battery mode) | ±1% | |
Transfer time | AC to DC :Zero Inverter to Bypass: Zero | |
Over current protection | Line Mode:10min@100%~130%;Battery Mode:30s@100%~130% | |
Outlet | Hard Wiring with Terminal Block | |
Harmonic Distortion | ≤2%THD(Linear Load);≤5%THD(Non-Linear Load) |
2.Input
Nominal Voltage | 160~300VAC@full load (110~300VAC@half load) |
Input Frequency | 46~54Hz / 56~60Hz |
Efficiency | 90% (AC mode) 90%(Battery Type) |
Noise Filtering | Full time EMI/RFI filtering |
Over current protection | by AC fuse or by re-settable over current protector |
AVR Range (2 Bucks,2 Boosts) | Enhanced Buck: +15% of selected nominal voltage Buck mode: +5% of selected nominal voltage Boost mode: -5% of selected nominal voltage Enhanced Boost: -12.5% of selected nominal voltage |
Phase | Single phase with ground |
3.Battery
Battery type | Sealed Lead Acid Battery |
Rated Charging Voltage | 220.8Vdc |
Typical backup time | >5min |
Charging method | Smart pulse charging with two charging modes. Quick charging when battery is not fully charged, trickle charging when battery is 90% fully charged. |
Charging current(MAX) | 1.0A(6KS,10KS:4.0/8.0A) |
Protection | Over current protection & Over charging voltage protection (SCR control) Thermal protection (CPU control) When temperature inside UPS is over 45°C,charger will stop charging for 2.5 minutes followed by an 1.5 minutes charging. The cycle will be repeated until the temperature is lower than 44°C. |
Temperature Compension | Yes |
Numbers of Battery | 20 |
4.Optional Features
ECO Mode | Support |
CVCF | Support |
PDU | Support |
Remote Panel | Wired Type,Up to 100M Length |
Parallel Redundancy | Up to 4 Units maxium(Option) Up to 4 Units maxium(Option) |
5.Environmental and Safety
Operating Temperature | 0°C to 40°C (32°F to 104°F) | |
Transit/storage Temperature | -15°C to 55°C (5°F to 131°F) | |
Relative Humidity | 20-90%(NON-CONDENSING) | |
Operating Altitude | 0 ~ 3000 meters | |
Audible noise | Less than 50 dBA | |
Safety Markings | BSMI | CE |
EMC | Class B, EN50091-2, FCC part15, IEC1000-2-2 | |
Quality control system | ISO 9001:2000 | |
Noise Level | <60dB@1 Meter |
6.Indicator
LED Version | Load Level/Battery Level/Battery;Mode/AC Mode/Bypass Mode/Fault |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously Sounding |
7.Interface
Smart RS-232 | Software supports Windows Family.Sun Solaris, IBM Aix,Compaq True64,SGIIRIX ,FreeBSD.HP-UX,and MAC |
USB (Option) | Windows Family& MAC |
Internal Slot (Option) | SNMP/AS400 Relay Card/Rs485 |
EPO(Option) | Support Emergency Shutdown |
8.Physical
Dimensions: (D×H×W) | 570*260*717mm | |
N.W/G.W(kg) | 6KVA:90 6KS:35 | 10KVA:93 10KS:38 |
Packing | PBP standard Packing,Export carton for each unit |
3.Pictures
4. Typical Application
Servers, Data centers, Critical network devices, Sensitive electronic equipment, Telecom
Main Features:
Sine-wave output: True sine-wave output with less than 3% THD.
Double Conversion Design: Zero transfer/ complete isolation of input AC.
UPS Monitoring Software: Powerful true RS232 communication via the enclosed software to manage and safely shutdown operating systems.
Network RJ45/11 protection: Complete powerful network and phone line surge protection.
AC Surge Suppressor: Powerful multi-stage surge components that exceed IEEE requirements.
SNMP Slot Option: Allows for remote monitoring and control via www.
Sleep Mode: Worry free battery management. The unit turns itself off after ten seconds to conserve battery power when no power needs are detected.
Battery level indicators: LED’s indicate battery levels.
Load Sensing: The incorporated LED load indicators allow IT professionals to manage backup time and balance power loads.
Low Battery indicators: The low battery level indicator will warn of eminent UPS shutdown two full minutes before unit shuts down.
Replace Battery indicators: A preventative measure that indicates when batteries must be replaced to prevent server crashes.
Output | C1KVA/C1KS | C2KVA/C2KS | C3KVA/C3KS |
Power Levels crated at nominal inputs | 1000VA/700W | 2000VA/1400W | 3000VA/2100W |
Output Voltage | 208VAC/220VAC/230VAC/240VAC | ||
Voltage Waveform | Sine wave | ||
Crest Factor | 3:1 | ||
Output Frequency (Synchronized to Mains) | 46~54Hz or 56Hz - 64Hz (Line mode) 50/60HZ/ ±0.05Hz( Battery mode) | ||
Regulation (Nominal) | ±1% | ||
Regulation (Battery mode) | ±1% | ||
Transfer time | 0 ms; less than 4 ms from inverter to bypass and vice versa | ||
Over current protection | Line Mode:10min@100%~130%; Battery Mode:30s@100%~130% | ||
Outlet | IEC*4/IEC*6/IEC*4+Terminal | ||
Harmonic Distortion | ≤2%THD(Linear Load) ≤5%THD(Non-Linear Load) |
2.Input
Input | C1KVA/C1KS | C2KVA/C2KS | C3KVA/C3KS |
Nominal Voltage | 160~300VAC@full load (110~300VAC@half load) | ||
Input Frequency | 46~54Hz / 56~60Hz | ||
Efficiency | 87% (AC mode)/83%(Battery Type) | ||
Noise Filtering | Full time EMI/RFI filtering | ||
Over current protection | by AC fuse or by re-settable over current protector |
AVR Range (2 Bucks, 2 Boosts) | Enhanced Buck: +15% of selected nominal voltage Buck mode: +5% of selected nominal voltage Boost mode: -5% of selected nominal voltage Enhanced Boost: -12.5% of selected nominal voltage |
Phase | Single phase with ground |
3.Battery
Battery type | Sealed lead acid Battery |
Rated Charging Voltage | 41.0Vdc / 81.9Vdc / 109.2Vdc |
Typical backup time | >5min |
Charging method | Smart pulse charging with two charging modes. Quick charging when battery is not fully charged, trickle charging when battery is 90% fully charged. |
Charging current(MAX) | 1.0A(C1KS-C3KS:4.0/8.0A) |
Protection | Over current protection & Over charging voltage protection (SCR control) Thermal protection (CPU control) When temperature inside UPS is over 45°C, charger will stop charging for 2.5 minutes followed by an 1.5 minutes charging. The cycle will be repeated until the temperature is lower than 44°C. |
Temperature Compension | Yes |
Numbers of Batteries | 3 / 8 / 8 |