AAC Wasp/AAC 100 / aluminum stranded conductor/ concentricalli stranded conductor
USD $0.16 - $0.65 /Meter
Min.Order:1000 Meters
Zhengzhou Sanhe Cable Co., Ltd.
AAC Wasp/AAC 100 / aluminum stranded conductor/ concentricalli strande
Product Description
Overhead line Conductor--AAC
Standard: DIN 48201 NIS231 BS215 PART 1:1970
Specification: aac are composed by bare concentric-lay-stranded aluminum wires with a straight round central aluminum wire surrounded by one or more layers of helically layed aluminum wires.
Application:
*AAC are used in overhead power transmission and distribution lines with various grade voltages.
*Under the same weight,AAC is with higher DC resistance and lower costthan copper conductor.
*Aluminum is light and is easy to lay.
Manufacturing Standard: ASTM B231 B232, BS 215 , DIN 48201, CSA C49,NFC 34120
We can also manufacture AAC Cable according to customers special requirements.
Stranded 1350 aluminum conductors shown in this section of data are classified, as follows:
Class AA | For bare conductors usually used in overhead lines. |
Class A | For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required. |
Class B | For conductors to be insulated with various materials and for conductors indicated under Class A where greater flexibility is required. |
Class C | For conductors where greater flexibility is required |
Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available.
Note: Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible
AAC bare conductors meet or exceed the following ASTM specifications:
B-230 Aluminum Wire, 1350-H119 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-400 Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors concentrically stranded.
AAC Technical Characteristics Based on Standard DIN 48201 / DIN EN50182
Technical Characteristics Based on Standard BS 215-1 | |||||||
Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load |
mm2 | No./mm | mm2 | mm | kg/km | Ω/km | kN | |
MIDGE | 22 | 7/2.06 | 23.33 | 6.18 | 64 | 1.227 | 3.99 |
ANT | 50 | 7/3.10 | 52.83 | 9.3 | 145 | 0.5419 | 8.28 |
FLY | 60 | 7/3.40 | 63.55 | 10.2 | 174 | 0.4505 | 9.9 |
WASP | 100 | 7/4.39 | 106 | 13.17 | 290 | 0.2702 | 16 |
HORNET | 150 | 19/3.25 | 157.6 | 16.25 | 434 | 0.1825 | 25.7 |
CHAFER | 200 | 19/3.78 | 213.2 | 18.9 | 587 | 0.1349 | 32.4 |
COCKROACH | 250 | 19/4.22 | 265.7 | 21.1 | 731 | 0.1083 | 40.4 |
BUTTERFLY | 300 | 19/4.65 | 322.7 | 23.25 | 888 | 0.08916 | 48.75 |