Specifications
* Time delay on make
* 3 minutes time delay
* 5 minutes time delay
* Knob adjustable time delay from .03-10 minutes
Time delay & time relay
Works with anticipator thermostat
* Time delay on make
* QD-100 3 minutes time delay
* QD-101 5 minutes time delay
* QD-068 Knob adjustable time delay from .03-10 minutes
Installation
1. Disconnect power.
2. Connect terminals in series with the starting device as shown in the system diagram below.
3. For 24 VAC circuits, apply control as packaged. For 120/240 VAC circuits, cut the jumper wire.
4. Select the desired time delay.
5. Reapply power, check operation.
6. Trickle current bypass resistor T1 to T3 < 1k ohm.
Specification
Input:
Line Voltage: 18-240 VAC/VDC
Line Frequency: 50/60 HZ
Output:
Output Ratings:
Maximum: 1.5 amps
Minimum: 40 mA
Inrush: 15 amps
Time Delay: .03-10 mins. adjustable
3 or 5 minute fixed
Mode of Operation
When power is applied to the input, the time delay begins. After the time delay is complete, the load energizes and remains energized as long as power is applied. The control is reset by removing power during or after the time delay period.
The QD-068 provides thermostat interruption protection, even in the presence of a trickle current.