Specifications
*Time delay on break*QD-207 3 minutes time delay
*QD-208 5 minutes time delay
*QD-209 adjustable time delay from .03-10 min
Time relay / time delay on break
Works with anticipator thermostats
*QD-207 3 minutes time delay
*QD-208 5 minutes time delay
*QD-209 adjustable time delay from .03-10 minutes
*QD-208 5 minutes time delay
*QD-209 adjustable time delay from .03-10 minutes
Installation
1. Disconnect power.
2. Connect terminals as shown in the wiring diagram below.
3. Select desired time delay (adjustable models only).
4. Reapply power, check operation.
Specification
Input:
Line Voltage: 18-240 VAC
Line Frequency: 50/60 HZ
Output:
Output Ratings:
Maximum: 1.0 amps
Minimum: 40 mA
Inrush: 10 amps
Time Delay:
3 or 5 minute fixed
.03-10 minutes. adjustable
Mode of Operation
Upon initial thermostat closure, the load is energized. When the thermostat opens or there is a loss of power, the load is de-energized and the delay period begins. The compressor will not start again during the delay period.
Timing Diagram
System Diagram