Specifications
Oil reclaimerAcid removing and carbon filtering out
Water degasification and moisture removing.
·Field live-wire filtration of power transformer oil;
·High-efficiency & good quality purification of high pressure transformer oil;
·Regeneration of waste transformer oil;
·Random computerized inspection for pressure-resistant values of insulating oil.
Water content | PPM | ≤5 |
Gas content | % | ≤0.1 |
Impurities size | μm | ≤5,without free carbon |
Breakdown voltage | KV | ≥65(IEC 156) |
Flash point | °C | ≥135 |
Interfacial tension | mN/m | ≥ 40(ASTM D-971) |
Ethyne content | / | 0 |
Color | / | Appearance clear, L0.5-L1.0 (ASTM D-1524) |
Water-soluble acid | PH | ≥5.4 |
Acid value | MgKOH/g | ≤0.01(IEC296) |
Dielectric loss factor | 90°C | ≤0.005(IEC247) |